APC manual Technical Specifications, APC BC300 Series 40 kW Technical Data

Models: BC300 Series

1 38
Download 38 pages 11.26 Kb
Page 35
Image 35

Technical Specifications

7.0Technical Specifications

7.1APC BC300 Series 40 kW Technical Data

 

Voltage

3 x 208Y/120 or

450V Delta

3 x 480Y/277

 

 

208V Delta

 

 

 

 

 

 

 

Input

Rated input current

146Amps

75 Amps

63Amps

 

 

 

 

 

 

Voltage tolerance

 

 

 

 

- Utility

+10 / -15

+10 / -15

+10 / -15

 

- Bypass

+/- 10

+/- 10

+/- 10

 

 

 

 

 

 

Frequency

60Hz

60Hz

60Hz

 

 

+/- 6%

+/- 6%

+/- 6%

 

 

(standard)

(standard)

(standard)

 

 

 

 

 

 

Current distortion

0-5% THD

0-5% THD

0-5% THD

 

 

 

 

 

 

Bypass tolerance

+/- 10%

+/- 10%

+/- 10%

 

 

 

 

 

Output

Voltage

3 x 208Y/120

3 x 450Y/277 or

3 x 480Y/277 or

 

 

 

3 x 450 Delta

3x 480 Delta

 

 

 

 

 

 

Voltage tolerance

 

 

 

 

- Static symmetrical load

+/- 1

+/- 1

+/- 1

 

- Static asymmetrical load

+/- 3

+/- 3

+/- 3

 

- Load step

+/- 5

+/- 5

+/- 5

 

 

 

 

 

 

Voltage distortion

0 - 3% (linear

0 - 3% (linear

0 - 3% (linear

 

 

load)

load)

load)

 

 

 

 

 

 

Frequency

60Hz

60Hz

60Hz

 

- Utility synchronized

+/- 6%

+/- 6%

+/- 6%

 

- Free-running

+/- 0.1%

+/- 0.1%

+/- 0.1%

 

 

 

 

 

 

Overload capacity

 

 

 

 

- Utility operation 60 seconds

250%

250%

250%

 

- Utility operation 10 minutes

150%

150%

150%

 

- Battery operation 60 seconds

150%

150%

150%

 

- Battery operation 10 minutes

125%

125%

125%

 

 

 

 

 

 

Rated output current

111 Amps

51 Amps

48 Amps

 

 

 

 

 

General

Temperature

 

 

 

 

Ambient

32 - 104 o F

32 - 104 o F

32 - 104 o F

 

Ideal

77 o F

77 o F

77 o F

 

Humidity (non condensing)

Max 95%

Max 95%

Max 95%

 

 

 

 

 

 

Audible Noise (typical)

<65 dBa

<65 dBa

<65 dBa

 

 

 

 

 

 

Efficiency

 

 

 

 

AC to AC normal operation

95%

95%

95%

 

AC to AC economy mode

97%

97%

97%

 

 

 

 

 

 

Heat dissipation - kW (BTU)

 

 

 

 

Full rated load normal operation

2.11 (7185)

2.11 (7185)

2.11 (7185)

 

Full rated load economy mode

1.67 (5688)

1.67 (5688)

1.67 (5688)

 

0.8 PF load, normal operation

1.68 (5748)

1.68 (5748)

1.68 (5748)

 

0.8 PF load, economy mode

1.33 (4551)

1.33 (4551

1.33 (4551)

 

 

 

 

 

990-1401

Installation Guide APC BC300 Series 40kW 208/450/480V UPS

35

Page 35
Image 35
APC manual Technical Specifications, APC BC300 Series 40 kW Technical Data