APC BC300 Series Installation of External Batteries and Battery Breaker, Physical, Environmental

Models: BC300 Series

1 38
Download 38 pages 11.26 Kb
Page 27
Image 27

Installation

3.5.6.2 Power, Physical, and Environmental Specifications.

Item

Specification

 

 

Power

 

 

 

Turn on voltage:

> 22 VDC

 

 

Turn off voltage:

< 16 VDC

 

 

Current draw (normal operation):

90 mADC

 

 

Current draw (voltage < 16 VDC):

< 1 mADC

 

 

Physical

 

 

 

Size (H xW x D):

44 x 432 x 127 mm (1.75 x 17.0 x 5.0 in)

 

 

Weight:

1.81 kg (4.02 lb)

 

 

Shipping weight:

3.65 kg (8.12 lb)

 

 

Environmental

 

 

 

Elevation (above MSL):

 

- Operating

0 to 3000 m (0 to 10,000 ft)

- Storage

0 to 15 000 m (0 to 50,000 ft)

 

 

Temperature:

 

- Operating

0 to 45˚C (32 to 113˚F )

- Storage

-20 to 70˚C (-4 to 158˚F)

 

 

Relative humidity:

 

- Operating

0 to 95%, non-condensing

- Storage

0 to 95%, non-condensing

 

 

Electromagnetic immunity:

FCC Class A

 

EN50082-1 verified

 

 

3.6Installation of External Batteries and Battery Breaker

Some units are connected to optional external batteries in a separate cabinet or rack. External batteries must be installed and connected to the UPS by an authorized service personnel familiar with UPS battery installations and applicable building and electrical codes.

3.6.1 Battery Installation

WARNING

Full voltage and current are always present at the battery terminals. The batteries used in this system can produce dangerous voltages, extremely high currents, and may cause a risk of electric shock. They may cause severe injury if the terminals are shorted together or to ground (earth). You must be extremely careful to avoid electric shock and burns caused by contacting battery terminals or shorting terminals during battery installation. Do not touch uninsulated battery terminals.

Only authorized service personnel familiar with battery systems and required precautions may install and service the batteries. The installation must conform to national and local codes. Keep unauthorized personnel away from batteries.

990-1401

Installation Guide APC BC300 Series 40kW 208/450/480V UPS

27

Page 27
Image 27
APC BC300 Series Installation of External Batteries and Battery Breaker, Power, Physical, and Environmental Specifications