APC BC300 Series manual Triple Chassis Power Considerations, Determining Power Requirements

Models: BC300 Series

1 38
Download 38 pages 11.26 Kb
Page 24
Image 24

Installation

3.5.4.4 Triple Chassis Power Considerations

The Triple Chassis receives its power from the UPS through the supplied 24 VDC universal adapter. The total current required by your management products must not exceed the 850 mA limit of the power adapter. See “Determining power requirements”.

3.5.4.5 Determining Power Requirements

To determine the total amount of current required by your management products, add the individual current requirements for each management product to be installed with the APC BC300 Triple Chassis to the current requirements of the chassis itself.

Management Product

Draw (mA)

 

 

Share-UPS 8-port Interface Expander

65

 

 

Expansion Chassis

30

 

 

Triple Chassis

20

 

 

APC BC300 Triple Chassis

90

 

 

Web/SNMP Management Card

110

 

 

Interface Expander

45

 

 

Out-of-Band Management Card

35

 

 

Environmental Monitoring Card

60

 

 

Isolated Extension Cable

50

 

 

Remote Power-Off Device

35

 

 

3.5.5 Troubleshooting

The following table shows the solutions to common problems with the operation of the Triple Chassis

Problem

Possible Cause

Solution

 

 

 

Status LED is off

The chassis is not

See “Powering the APC BC300

 

receiving adequate

Triple Chassis”, and verify that you

 

power.

are not exceeding current

 

 

requirements.

 

 

 

Status LED is flashing

The chassis has not been

Configure the Silcon Triple Chassis.

quickly

configured.

See the Web/SNMP Management

 

 

Card Installation Guide on the CD

 

 

for more information.

 

 

 

Status LED is flashing

The chassis is not

Verify that the supplied UPS cable is

slowly

communicating with the

properly connected to the Triple

 

UPS.

Chassis and to a communications

 

 

port on the UPS.

 

 

 

Attached management

The management

You may be able to upgrade the

product cannot identify

firmware does not

firmware of the management

UPS model or nominal

support 3-phase UPSs.

product. Call APC Customer

output voltage.

 

Support.

 

 

 

3.5.5.1 If Problems Persist

For problems not covered in the troubleshooting chart or for persistent problems, follow this procedure:

990-1401

24

Installation Guide APC BC300 Series 40kW 208/450/480V UPS

Page 24
Image 24
APC BC300 Series Triple Chassis Power Considerations, Determining Power Requirements, Troubleshooting, If Problems Persist