CHAPTER 4: TROUBLESHOOTING

Condition

PowerView Message

Reason

Corrective Action

 

 

 

 

General Fault

Input circuit breaker

The input circuit breaker on the

Option 1: If this occurs in

(continued)

tripped open.

UPS tripped open. Input voltage is

conjunction with an overload

 

 

disconnected from the UPS.

condition, decrease the load

 

 

 

and reset the breaker.

 

 

 

Option 2: If no overload

 

 

 

condition exists, reset the

 

 

 

breaker. If the breaker trips

 

 

 

open again, call contract

 

 

 

service provider or APC

 

 

 

Technical Support.

 

 

 

 

 

System level fan failed.

A cooling fan in the UPS frame

Call contract service provider

 

 

failed.

or APC Technical Support.

 

 

 

 

 

The Redundant

The intelligence module in the

Replace the intelligence

 

Intelligence Module (IM)

lower IM slot has failed or is not

module. Refer to module

 

is in control.

installed. The intelligence module

replacement procedure.

 

 

in the upper IM slot is managing all

 

 

 

activity.

 

 

 

 

 

 

IIC inter-module

The communications between the

Call contract service provider

 

communications failed.

MIM and at least one other module

or APC Technical Support.

 

 

failed.

 

 

 

 

 