CHAPTER 2: BASIC COMMANDS

Set the Correct Output Voltage

1.Press the ‘Esc’ button until the Main Menu appears. Use the up and down arrow keys to choose ‘Setup’, and ENTER to select.

Control Logging

Status Display

>Setup Diags

Accessories Help

2.Use the arrow keys and ENTER to select ‘Other’.

Settings:

Alarms

Shutdown

Bypass

Defaults

Copy

Output Freq

>Other

3.If the output voltage is not correct for your application, use the arrow keys, and ENTER to select ‘Output’. The cursor will move to the voltage field, as the up and down arrows scroll through available choices. Choose the desired voltage setting and press ENTER to select.

Self Test: Enabled

UPS ID: UPS_IDEN

Vout Reporting: AUTO

>Output: 208V

Supply Power to the Load Equipment

The Symmetra LX must be turned on before executing this procedure.

1.Press ‘Esc’ until the Main Menu appears. Use the arrow keys to choose ‘Control’ and ENTER to select.

>Control Logging

Status Display

Setup Diags

Accessories Help

2.Use the arrow keys to choose ‘Turn UPS Output On’ and ENTER to select. NOTE: You must scroll to a second page of choices.

Graceful Turn Off

Start Runtime Cal

>Turn UPS Output On

3.Confirm choice by selecting ‘YES’.

Confirm:

Turn UPS On

CANCEL

>YES, Turn UPS On

4.There will be clicking sounds and this message will appear. NOTE: You may be given one or more override warnings. Answer these by selecting ‘Start Now’.

UPS HAS BEEN COMMANDED

TO TURN LOAD POWER ON