APC SYBATT manual Basic Commands, Supply Power to the UPS

Models: SYBATT

1 25
Download 25 pages 32.62 Kb
Page 7
Image 7

CHAPTER 2: BASIC COMMANDS

Basic Commands

Supply Power to the UPS

This procedure supplies power to the Symmetra LX and does not supply power to the equipment connected to the UPS.

1.Turn ON the AC utility power to the UPS

2.Switch ON the circuit breakers for all connected equipment.

a.If connected equipment is hardwired, check that the output circuit breakers in the distribution panel are turned ON.

b.If connected equipment is plugged into the UPS ! , check that each UPS PDU output circuit breaker " is switched ON.

3.Switch ON the UPS input circuit breaker # .

4.Turn ON the UPS system enable switch $ .

To start the UPS when there is no AC utility power present, press and hold either of the cold start buttons % for four seconds.

5.After initialization, the monitoring screen appears, providing a view of operating parameters.

Chg100% Load 000%

220 Vin 000 Vout 60Hz Runtime: 00hr 30min

3

Page 7
Image 7
APC SYBATT manual Basic Commands, Supply Power to the UPS