CHAPTER 3: MENU COMMANDS
Setup Menu
The Setup Menu allows the user to customize the UPS functionality.
| 
 | Menu Item | 
 | Function | Options | 
| 
 | 
 | 
 | 
 | 
 | 
| 
 | Shutdown | 
 | Sets the shutdown parameters in the event of a | None | 
| 
 | 
 | utility power failure. | 
 | |
| 
 | 
 | 
 | 
 | |
| 
 | 
 | 
 | 
 | 
 | 
| 
 | Low Batt(ery) | 
 | Sets the number of minutes an audible alarm | 2 (default), 5, 7, 10, 12, 15, | 
| 
 | Dur(ation) | 
 | sounds before the UPS shuts down due to battery | 18, or 20 minutes | 
| 
 | 
 | 
 | exhaustion. | 
 | 
| 
 | 
 | 
 | 
 | |
| 
 | Shutdown Delay | Sets the additional runtime for computer issuing | 0, 20 (default), 60, 120, 240, | |
| 
 | 
 | 
 | shutdown command if it needs additional time to | 480, 720, or 960 seconds | 
| 
 | 
 | 
 | shut itself down. | 
 | 
| 
 | 
 | 
 | 
 | |
| 
 | Return Delay | Sets the delay interval that allows utility power to | 0 (default), 20, 60, 120, 240, | |
| 
 | 
 | 
 | stabilize before the system goes back online after a | 480, 720, or 960 seconds | 
| 
 | 
 | 
 | utility power failure. | 
 | 
| 
 | 
 | 
 | 
 | 
 | 
| 
 | Return Battery | 
 | Sets the minimum battery capacity necessary | 0 (default), 15, 25, 35, 50, | 
| 
 | Capacity | 
 | before repowering the load when returning from an | 60, 75, or 90 seconds | 
| 
 | 
 | 
 | extended utility power failure. | 
 | 
| 
 | 
 | 
 | 
 | 
 | 
| 
 | Defaults | 
 | Sets all settings to factory defaults. | 
 | 
| 
 | 
 | 
 | 
 | 
 | 
| 
 | Output Freq(uency) | 
 | The UPS output will phase lock to the input within | 50 ±3 Hz, 50 ± 0.1 Hz, 60 ± | 
| 
 | 
 | 
 | this range. | 3 Hz, 60 ± 0.1 Hz, Full range | 
| 
 | 
 | 
 | 
 | tracking | 
| 
 | 
 | 
 | 
 | 
 | 
13