Troubleshooting – Status and Alarm Messages

Display Message

Meaning

Corrective Action

 

 

 

System Not Synchro-

The system cannot synchronize to

Option 1: Decrease the input fre-

nized to Bypass.

bypass. The mode may not be avail-

quency sensitivity.

 

able.

Contact APC Customer Support

 

 

(see back cover).

 

 

Option 2: Correct the bypass input

 

 

voltage to provide acceptable voltage

 

 

on frequency.

 

 

 

UPS In Bypass Due To

The UPS has transferred to Bypass

Contact APC Customer Support

Fault.

Mode because a fault has occurred.

(see back cover).

 

 

 

UPS In Bypass Due To

The load exceeded the power

Decrease the load.

Overload.

capacity. The UPS has switched to

 

 

Bypass Mode.

 

 

 

 

UPS Is Overloaded.

The load exceeded the system power

Option 1: Decrease the load.

 

capacity.

Option 2: Check the load distribution

 

 

on the 3 phases via the display. If the

 

 

load is unevenly distributed, adjust

 

 

the load distribution.

 

 

 

Weak Batt(s) Detected.

One or more weak batteries detected.

Replace the weak batteries.

Reduced Runtime.

 

 

 

 

 

XR Battery Fuse Blown.

XR Battery Fuse blown. Runtime is

Replace the blown fuse in XR Enclo-

 

lower than expected.

sure (only applicable if your installa-

 

 

tion includes an XR

 

 

Enclosure).

 

 

 

36

Smart-UPS® VT 10-40 kVA 400V, 208V, 200V – Operation

990-2282A-001

Page 42
Image 42
APC VT manual Display Message Meaning Corrective Action