Troubleshooting – Status and Alarm Messages
Display Message | Meaning | Corrective Action | 
  | 
  | 
  | 
System Not Synchro-  | The system cannot synchronize to  | Option 1: Decrease the input fre-  | 
nized to Bypass.  | bypass. The mode may not be avail-  | quency sensitivity.  | 
  | able.  | Contact APC Customer Support  | 
  | 
  | (see back cover).  | 
  | 
  | Option 2: Correct the bypass input  | 
  | 
  | voltage to provide acceptable voltage  | 
  | 
  | on frequency.  | 
  | 
  | 
  | 
UPS In Bypass Due To  | The UPS has transferred to Bypass  | Contact APC Customer Support  | 
Fault.  | Mode because a fault has occurred.  | (see back cover).  | 
  | 
  | 
  | 
UPS In Bypass Due To  | The load exceeded the power  | Decrease the load.  | 
Overload.  | capacity. The UPS has switched to  | 
  | 
  | Bypass Mode.  | 
  | 
  | 
  | 
  | 
UPS Is Overloaded.  | The load exceeded the system power  | Option 1: Decrease the load.  | 
  | capacity.  | Option 2: Check the load distribution  | 
  | 
  | on the 3 phases via the display. If the  | 
  | 
  | load is unevenly distributed, adjust  | 
  | 
  | the load distribution.  | 
  | 
  | 
  | 
Weak Batt(s) Detected.  | One or more weak batteries detected.  | Replace the weak batteries.  | 
Reduced Runtime.  | 
  | 
  | 
  | 
  | 
  | 
XR Battery Fuse Blown.  | XR Battery Fuse blown. Runtime is  | Replace the blown fuse in XR Enclo-  | 
  | lower than expected.  | sure (only applicable if your installa-  | 
  | 
  | tion includes an XR  | 
  | 
  | Enclosure).  | 
  | 
  | 
  | 