APC VT manual How to store the battery modules, Replaceable parts only trained personnel

Models: VT

1 44
Download 44 pages 58.32 Kb
Page 32
Image 32

Maintenance – Parts Replacement

How to store the battery modules

The battery modules must be stored indoors and with their protective packaging still in place.

Ambient temperature:

-15° to 40°C/5°F to 104°F

Relative Humidity:

25-85% Non-condensing

Storage place free from vibration, dust, direct sunlight, and moisture.

Stored batteries should be recharged at regular intervals depending on the storage temperature:

Storage Temperature

Recharge interval

 

 

-15° to 20°C/5°F to 68°F

9 months

 

 

20° to 30°C/68°F to 86°F

6 months

 

 

30° to 40°C/86°F to 104°F

3 months

 

 

Caution: Do not store the batteries for more than 12 months.

Replaceable parts (only trained personnel).

Part

APC Part No.

 

 

Battery Module

SYBT4

Network Management Card with temperature sensor

AP9619

 

 

APC recommends that a whole battery module (four batteries) is replaced at the same time to ensure optimal runtime. However, it is only necessary to replace two batteries at the same time. See section How to replace and install a battery module, Directions for replacement.

Note

26

Smart-UPS® VT 10-40 kVA 400V, 208V, 200V – Operation

990-2282A-001

Page 32