Operation – Operation Procedures

Turn the internal mechanical bypass lever upwards to activate it. The load will now be supported directly by utility/mains power.

Reinstall the Front Panel.

Single System – turning into external bypass.

In bypass operation the batteries are still powered. If a total power off is required the batteries must be pulled out to the red disconnect line, see the section How to perform a total power off.

Warning

Chrg 100%

Load 000%

xxxVin 000Vout x0Hz Runtime: 0hr 0m

Use

UPS into Bypass Do Self Test Simulate Power Fail Start Runtime Cal

Press

Use

 

 

 

Press

 

 

 

Control Logging

Status Display

Setup Diags

Help

Press

Use

Press

 

Confirm:

 

 

UPS into

Bypass

 

NO, ABORT

 

 

YES, UPS

into Bypass

From the external MBP: Turn the bypass switch (Q003) to position “1” (ON).

If the UPS has to be completely isolated/ removed, see the section How to perform a total power off.

From the external MBP: Turn the output switch (Q002) to position “0” (OFF).

8

Smart-UPS® VT 10-40 kVA 400V, 208V, 200V – Operation

990-2282A-001

Page 14
Image 14
APC VT manual Single System turning into external bypass