Maintenance – Parts Replacement

Follow the below procedures if you need to change or add a battery module, e.g. if you receive a display

message reporting a bad battery, or if you need to add batteries for increased runtime.

XRUPS

When removing Battery Modules, start from

Holding the battery handle, gently push the

the highest level and work down.

battery upwards and pull it halfway out of

 

the enclosure. A lock mechanism prevents it

 

from being pulled all the way out.

To release the battery from the lock

 

mechanism, gently push the battery upwards

 

again and pull it out, while another person

 

supports the battery.

 

Installation. If additional batteries are needed for extra runtime, or if you install battery replacement modules, be aware of the following:

Caution

Caution

Batteries must be replaced by trained personnel only (see the section General safety prior to Battery Module replacement).

Do not install Battery Modules in the UPS until you are ready to power up the system. Disregarding this caution can result in a deep discharge of the batteries and cause permanent damage. The time between battery installation and powering up the UPS should not exceed 72 hours or 3 days.

990-2282A-001

Smart-UPS® VT 10-40 kVA 400V, 208V, 200V – Operation

31

Page 37
Image 37