Operation – Operation Procedures

How to turn load OFF/ON via the display interface

Disconnecting the UPS output to the load does NOT de-energize the UPS! Always follow the total power off procedure if you need to de-energize the UPS in emergency Warning situations, see section How to perform a total power off!

Turn Load OFF – How to disconnect the UPS output to the load equipment.

Press Use

Chrg 100%

Load 000%

xxxVin 000Vout x0Hz Runtime: 0hr 0m

Use

 

 

 

Press

Use

 

 

 

Turn Load Off

If the UPS is running in parallel operation this procedure must be carried out on each UPS.

Control

Logging

Status

Display

Setup

Diags

 

Help

Confirm:

Turn Load OFF

NO, Abort

YES, Turn Load OFF

Press

Press

Turn load ON – How to connect the UPS output to the load equipment.

Press Use

Chrg 100%

Load 000%

xxxVin 000Vout x0Hz Runtime: 0hr 0m

Press

Control Logging

Status Display

Setup Diags

Help

Use

 

 

 

Press

Use

 

 

 

Turn Load On

Confirm:

Press

If the UPS is running in parallel operation this procedure must be carried out on each UPS.

Turn Load OFF

NO, Abort

YES, Turn Load ON

12

Smart-UPS® VT 10-40 kVA 400V, 208V, 200V – Operation

990-2282A-001

Page 18
Image 18
APC VT manual How to turn load OFF/ON via the display interface