Operation – Operation Procedures
12 Smart-UPS® VT 10-40 kVA 400V, 208V, 200V – Operation 990-2282A-001

How to turn load OFF/ON via the display interface

Turn Load OFF – How to disconnect the UPS output to the load equipment.
Turn load ON – How to connect the UPS output to the load equipmen t.
Warning

Disconnecting the UPS output to the load does NOT de-energize the UPS! Always follow

the total power off procedure if you need to de-energize the UPS in emergency

situations, see section How to perform a total power off!


If the UPS is running in parallel operation

this procedure must be carried out on each

UPS.


If the UPS is running in parallel operation

this procedure must be carried out on each

UPS.

Chrg 100%
Load 000%
xxxVin 000Vout x0Hz
Runtime: 0hr 0m
Press Control
Status
Setup
Logging
Display
Diags
Help
Use Press
Turn Load Off Press
Use
Confirm:
Turn Load OFF
NO, Abort
YES, Turn Load OFF
Use
Press
Chrg 100%
Load 000%
xxxVin 000Vout x0Hz
Runtime: 0hr 0m
Press Control
Status
Setup
Logging
Display
Diags
Help
Use Press
Turn Load On Press
Use
Confirm:
Turn Load OFF
NO, Abort
YES, Turn Load ON
Use
Press