Configuration – Settings
The Beeper setup. In the Beeper setup you can choose between the following options:
•Never: If you select this setting, the Beeper will be active at internal UPS errors only.
•PwrFail+30: If you select this setting, the Beeper will be active at internal UPS errors and at utility/ mains or bypass errors. The Beeper will only sound if the fault has been present for more than 30 seconds.
•PwrFail: If you select this setting, the Beeper will be active at internal UPS errors and at utility/ mains or bypass errors. The Beeper will sound immediately when the error is occurring.
•LOW BATT: If you select this setting, the Beeper will be active at internal UPS errors at utility/ mains or bypass errors, at power failures, and at a low battery level (if the UPS runs in battery operation).
24 |