Operation Procedures
How to turn into bypass
Single System – turning into internal bypass.
The load is not protected by the UPS and the power is not conditioned when the internal mechanical bypass lever is activated.
Caution
In bypass operation the batteries are still charged. If a total power off is required, the batteries must be pulled out to the red disconnect line, see the section How to perform a total power off.
Warning
This procedure is not applicable to parallel systems as the internal mechanical bypass lever is unavailable.
Note
If the UPS is running and controllable through the display, carry out steps 1 through 5. If not, go directly to step 6.
Note
Chrg 100%
Load 000%
xxxVin 000Vout x0Hz Runtime: 0hr 0m
Use
UPS into Bypass Do Self Test Simulate Power Fail Start Runtime Cal
Press | Use | Press |
| Control | Logging |
| Status | Display |
| Setup | Diags |
|
| Help |
Press | Use | Press |
| Confirm: |
|
| UPS into | Bypass |
| NO, ABORT |
|
| YES, UPS | into Bypass |
Check that the UPS is in bypass. The green | Remove the Front Panel from the UPS (see |
(LOAD ON) and the yellow (BYPASS) LEDs | the Receiving and Unpacking sheet referred |
are lit. | to under the section Companion manuals). |