Operation – Operation Procedures

Parallel System – turning into external bypass.

In bypass operation the batteries are still charged. If a total power off is required, the batteries must be pulled out to the red disconnect line, see the section How to perform a total power off.

Warning

Chrg 100%

Load 000%

xxxVin 000Vout x0Hz Runtime: 0hr 0m

Use

UPS into Bypass Do Self Test Simulate Power Fail Start Runtime Cal

Press

Use

Press

 

Control

Logging

 

Status

Display

 

Setup

Diags

 

 

Help

Press

Use

Press

 

Confirm:

 

 

UPS into

Bypass

 

NO, ABORT

 

 

YES, UPS

into Bypass

From the UPS: Check that all UPS units are in bypass on each of the displays.

From the external MBP: Turn the bypass switch (Q003) to position “1” (ON).

From the external MBP: Turn the output isolation breaker (Q004) to position “0” (OFF).

From the external MBP: Check that all output lamps are lit (Q002).

From the external MBP: Turn all input switches (Q001) to position “0” (OFF).

From the UPS: Disconnect the batteries by pulling them out to the red disconnect line.

For a total UPS shut down see the section How to perform a total power off.

From the external MBP: Check that the bypass lamp indication is lit (Q003).

From the external MBP: Check that the lamp

indication of the output isolation breaker is lit (Q004).

From the UPS: Turn OFF each UPS from the display via Control Turn Load off Yes, Turn Load off.

From the external MBP: Turn all output switches (Q002) to position “0” (OFF).

From the XR Enclosure(s) (if available): Set the DC disconnect switch (if available) to position OFF.

From the XR Enclosure(s) (if available): Disconnect the batteries by pulling them out to the red disconnect line.

990-2282A-001

Smart-UPS® VT 10-40 kVA 400V, 208V, 200V – Operation

9

Page 15
Image 15
APC VT manual Parallel System turning into external bypass