| 
  | Troubleshooting – Status and Alarm Messages  | ||
  | 
  | 
  | 
  | 
  | 
Display Message | Meaning  | 
  | Corrective Action  | 
  | 
  | 
  | 
  | 
  | 
  | 
PBus Communication  | Communication fault detected on the  | 
  | Check PBUS 1 or PBus 2 wiring.  | 
  | 
Fault on Cable 2.  | PBus 1 or PBus 2.  | 
  | If this does not help contact APC.  | 
  | 
  | 
  | 
  | 
  | 
  | 
PBus Termination Fault  | PBus 1 or PBus 2  | 
  | Check if termination is present. If this  | 
  | 
on Cable 1.  | termination is missing.  | 
  | does not help contact APC.  | 
  | 
  | 
  | 
  | 
  | 
  | 
PBus Termination Fault  | PBus 1 or PBus 2  | 
  | Check if termination is present. If this  | 
  | 
on Cable 2.  | termination is missing.  | 
  | does not help contact APC.  | 
  | 
  | 
  | 
  | 
  | 
  | 
Parallel Configuration  | The parallel system has not been con-  | 
  | Contact APC.  | 
  | 
Fault.  | figured correct. | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
Parallel Redundancy | The parallel redundancy has been | 
  | No corrective action is necessary. | 
  | 
Restored. | restored.  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
Replace Batt(s). | One or more Battery Modules need | 
  | See the section How to replace and | 
  | 
  | replacement (only applicable with  | 
  | install a battery module for proce- | 
  | 
  | internal batteries).  | 
  | dures.  | 
  | 
  | 
  | 
  | 
  | 
  | 
Runtime Is Below Alarm  | The predicted runtime is lower than  | 
  | Option 1: Allow the battery modules  | 
  | 
Threshold.  | the   | 
  | to recharge.  | 
  | 
  | alarm threshold. Either the battery  | 
  | Option 2: If possible, increase the  | 
  | 
  | capacity has decreased, or the load  | 
  | number of battery modules.  | 
  | 
  | has increased.  | 
  | Option 3: Reduce the load.  | 
  | 
  | 
  | 
  | Option 4: Decrease the alarm  | 
  | 
  | 
  | 
  | threshold.  | 
  | 
  | 
  | 
  | Contact APC Customer Support  | 
  | 
  | 
  | 
  | (see back cover).  | 
  | 
  | 
  | 
  | 
  | 
  | 
Site Wiring Fault.  | Wrong phase rotation on the input  | 
  | An electrician should check that the  | 
  | 
  | side. The UPS will continue to supply  | 
  | UPS has been wired properly.  | 
  | 
  | conditioned power from batt.  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
Shutdown Due To Low  | The UPS was in Battery Operation  | 
  | No corrective action is necessary.  | 
  | 
Battery.  | and shut down the load when no more  | 
  | Note: If the problem reoccurs, con-  | 
  | 
  | battery power was available.  | 
  | sider increasing the battery capacity.  | 
  | 
  | 
  | 
  | 
  | 
  | 
Static Bypass Switch  | The Static Bypass Switch has failed.  | 
  | Contact APC Customer Support (see  | 
  | 
Fault.  | 
  | 
  | back cover).  | 
  | 
  | 
  | 
  | 
  | 
  | 
System Failure Detected  | The system has detected an internal  | 
  | Check for other alarms and contact  | 
  | 
by Surveillance.  | error.  | 
  | APC customer support if the problem  | 
  | 
  | 
  | 
  | persists.  | 
  | 
  | 
  | 
  | 
  | 
  | 
System Start Up  | System configuration error. Unable to  | 
  | Check for other alarms and contact  | 
  | 
Configuration Failed.  | determine system voltage and/or  | 
  | APC customer support if the problem  | 
  | 
  | Enclosure size.  | 
  | persists.  | 
  | 
  | 
  | 
  | 
  | 
  | 
35  |