How to view the Status screens

Chrg 100%

Load 000%

xxxVin 000Vout x0Hz Runtime: 0hr 0m

Press Use

Operation – Operation Procedures

Press

Control Logging

Status Display

Setup Diags

Help

Use the UP/DOWN keys to go through the parameters:

View

Parameters

 

 

Voltage on all

Utility/mains voltage (V), bypass voltage (V), and output voltage (V) for each phase.

phases

 

 

 

Current on all

Utility/mains current (A), bypass current (A), and output current (A) for each phase.

phases

 

 

 

kVA and kW

Apparent power (kVA) and real power (kW) generated by the UPS and the connected

 

load.

 

 

Frequencies

Utility/mains frequency, bypass frequency, and output frequency in Hertz (Hz).

 

 

Load and batteries

Load: Percentage of the load in relation to the total UPS capacity.

 

 

Bat Voltage

Shows either the positive or negative half of the battery voltage (the lower value of the

 

two will appear).

 

 

Bat Cap

Percentage charge on the batteries in relation to the total battery capacity.

 

Runtime: The predicted runtime at the present load.

 

 

Batteries

Bat AmpHr: Battery capacity, including both external and internal batteries.

 

UPS Temp: The highest external battery temperature.

 

 

Alarm thresholds

Load: An alarm will be set when the load is above the threshold level.

 

Runtime: An alarm will be set when the runtime is below the threshold level.

 

 

Parallel Status

Local UPS is slave/master:

 

# of UPSs OK: Indicates the number of parallel UPS units that is OK.

 

# of UPSs fail: Indicates the number of parallel UPS that has failed.

 

 

Par load Status

KVA and KW: Total apparent power (kVA) and real power (kW) generated by the

 

parallel UPS units and the connected load.

 

Par redundancy: n+1, an alarm will be set if the redundancy level is below the threshold

 

level.

 

 

Parallel Operation

The parallel operation mode can be off, load on, requested bypass, in bypass due to fault

Mode

or maintenance.

 

 

Press the ESC key to return to the previous menus.