HEATER WITH OUTDOOR STACKLESS TOP | VENT TERMINAL (Outdoor) Stackless Top Installation |
1. Insert tabs into keyhole (4 places).
Outdoor Top
Pagoda Top (Shipped Loose with Heater)
2. Snap tabs into keyholes so as not to pull out.
Fig. # 8278.1 | Fig. #RP8280.1 |
|
Heaters must not be installed under an overhang of less than three (3) feet from the top of the heater. Three
(3)sides must be open in the area under the overhang. Roof water drainage must be diverted away from the heaters installed under overhangs with the use of gutters.
For U.S. installations,the point from where the flue products exit the heater must be a minimum of four (4) feet below, four (4) feet horizontally from, or one (1) foot above any door, window or gravity inlet into any building. The top surface of the heater shall be at least three (3) feet above any forced air inlet, or intake ducts located within ten
(10)feet horizontally.
For installations in Canada, pool heaters shall not be installed with the top of the vent assembly within 10 feet below, or to either side, of any opening into the building. Refer to the latest revisions of
4 foot |
|
|
Minimum |
|
|
| 4 foot |
|
| Minimum |
|
4 foot |
|
|
Minimum |
|
|
3 foot |
|
|
Minimum |
|
|
10 foot | 1 foot |
|
Minimum |
| |
Minimum |
|
|
Forced Air Inlet |
|
|
U.S. Installations only | Fig# | 8245.1 |
| 11 |
|