FIGURE 17

HEAT PUMP WITH ERV AND CO2 CONTROL (ON/OFF CYCLING)

SC SC SC

Completestat

Model #CS9B-THO or

Model #CS9BE-THO

24V COM G

Y1

Y2 O/B W2 W1/E

L

A

D

 

 

 

 

 

 

 

 

2

 

3

 

 

 

 

 

 

 

 

 

 

NOTE: Bard 8403-060

 

 

 

 

 

 

 

 

 

 

thermostat must be

Thermostat

 

 

 

 

 

 

 

 

 

in programmed

R

C

G

Y1

Y2 O/B W2

W1/E

L

A

YO/D

operation mode and

Bard #8403-060

 

 

 

 

 

 

 

 

 

 

 

in programmed fan

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

mode for ventilation

 

 

 

 

 

 

 

 

 

 

to function.

 

 

 

 

 

 

 

 

2

 

3

Low

R

RT

C

G

Y1

Y2

B/W1

W2

W3

L

A

D

6

Voltage

 

 

 

 

 

 

 

 

 

 

 

 

 

Term. Strip

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

RED/WHITE

 

 

 

 

 

 

 

 

 

 

 

 

 

BLACK/WHITE

 

 

 

 

 

 

 

 

6

 

 

 

ORANGE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BROWN/WHITE

 

 

 

 

 

 

 

 

 

 

 

 

PINK

 

 

 

 

 

 

 

 

 

 

 

 

 

PURPLE

 

 

 

 

 

 

 

 

 

 

 

 

 

3 4

2

1

5

6

ERV Wiring Harness

6 CO2 Control

Bard #8403-067

1

Factory installed jumper. Remove jumper and connect

4 Connect to "G" terminal when thermostat has "Occupancy Signal".

to N.C fire alarm circuit if emergency shutdown required.

 

 

2

Not needed below 15KW.

5

 

 

3 Additional wire required for dehumidification models.

6

Install a jumper between "G" and "A" only when thermostat without "Occupance Signal" is used.

If CS9B-THOC or CS9BE-THOC is used, connect "Brown/White" directly to "A" and do not use seperate CO2 controller.

MIS-3020

Manual

2100-549G

Page

27 of 59

Page 27
Image 27
Bard I48H1D, I42H1D, I36H1D, I60H1D, I30H1D installation instructions Heat Pump with ERV and CO2 Control ON/OFF Cycling