HEATING MODE OPERATION

CompleteStat should never energize “YO” terminals in conjunction with “B”, so relay “R2” will never energize, and neither will Economizer Ventilation Speed.

“Y1” and “Y2” signals will pass through NC contacts of relay “R2” contacts, and all heating operations will be normal.

VENTILATION MODE

The call for ventilation will never be disrupted with this control circuit. Anytime “A” signal from CompleteStat is present, the “VENTILATION SPEED” of the vent package will be energized. “A” Signal from thermostat will also energize relay “R4” (“Blower Interlock Relay”) completing a circuit from “R” to “G” through the “NO” contacts to ensure blower operations on the ventilation call.

FIGURE 24

MOTOR SPEED/CFM CONFIGURATION

VENT OPTION INTAKE/EXHAUST SPEEDS

WIRE COLOR

SPEED

NOM. CFM

 

 

 

BLACK

HI

525

BLUE

MED-HI

450

ORANGE

MED-LO

375

RED

LO

300

TO CHANGE SPEEDS, MOVE BROWN

WIRE WITH WHITE TRACE.

7961-755-2

Move pink wire to corresponding motor

speed for required economizer operation CFM. Factory setting is High (525 CFM).

PINK

BROWN/WHITE

Move brown/white wire to corresponding motor speed for required ventilation CFM. Factory setting is Medium Lo (375 CFM).

HI

SPEEDS

MED. HI

MOTOR

MED. LO

 

LO

7961-7554

BLACK

BLUE

ORANGE

RED

MIS-3271

Manual

2100-549G

Page

39 of 59

Page 39
Image 39
Bard I42H1D, I36H1D, I30H1, I60H1D, I48H1D Heating Mode Operation, Ventilation Mode, Motor SPEED/CFM Configuration