HEATING MODE OPERATION
CompleteStat should never energize “YO” terminals in conjunction with “B”, so relay “R2” will never energize, and neither will Economizer Ventilation Speed.
“Y1” and “Y2” signals will pass through NC contacts of relay “R2” contacts, and all heating operations will be normal.
VENTILATION MODE
The call for ventilation will never be disrupted with this control circuit. Anytime “A” signal from CompleteStat is present, the “VENTILATION SPEED” of the vent package will be energized. “A” Signal from thermostat will also energize relay “R4” (“Blower Interlock Relay”) completing a circuit from “R” to “G” through the “NO” contacts to ensure blower operations on the ventilation call.
FIGURE 24
MOTOR SPEED/CFM CONFIGURATION
VENT OPTION INTAKE/EXHAUST SPEEDS
WIRE COLOR | SPEED | NOM. CFM |
|
|
|
BLACK | HI | 525 |
BLUE | 450 | |
ORANGE | 375 | |
RED | LO | 300 |
TO CHANGE SPEEDS, MOVE BROWN
WIRE WITH WHITE TRACE.
Move pink wire to corresponding motor
speed for required economizer operation CFM. Factory setting is High (525 CFM).
PINK
BROWN/WHITE
Move brown/white wire to corresponding motor speed for required ventilation CFM. Factory setting is Medium Lo (375 CFM).
HI | SPEEDS | |
MED. HI | ||
MOTOR | ||
MED. LO | ||
|
LO
BLACK
BLUE
ORANGE
RED