RECOMMENDED CONTROL SEQUENCES
Several possible scenarios are listed below:
1.Use a programmable electronic thermostat with auxiliary terminal to control the ERV based on daily programmed occupance periods. Bard markets and recommends Bard Part
2.Use a motion sensor in conjuntion with a mechanical thermostat to determine occupancy in the structure. Bard markets the CS2000A for this use.
3.Use a DDC control system to control the ERV based upon a room occupancy schedule to control the ERV.
4.Tie the operation of the ERV into the light switch. The lights in a room are usually on only when occupied.
5.Use a manual timer that the occupants turn to energize the ERV for a specific number of hours.
6.Use a programmable mechanical timer to energize the ERV and indoor blower during occupied periods of the day.
NOTE: The ventilation package comes with a blower interlock function, but is disabled when it is shipped from the factory in case you do not utilize a thermostat with an occupancy output, or a occupancy sensor and must tie "A" terminal to "G" terminal to drive the ventilation package. If you do have a thermostat or control that does drive occupancy output, you will need to remove the tape from the orange wire located in the low voltage terminal box, and connect it to the "G" terminal to activate this function. (See Figures
CHANGING VENTILATION CFM RATES IN MANUAL MODE
! | WARNING |
| |
HAZARD OF ELECTRICAL SHOCK. |
| ||
ELECTRICAL SHOCK CAN RESULT |
| ||
IN SERIOUS INJURY OR DEATH. | 2 | ||
DISCONNECT THE REMOTE | - | ||
ELECTRIC POWER SUPPLY OR | |||
7961 | |||
SUPPLIES BEFORE SERVICING. | |||
|
To adjust the airflow ventilation rate, first refer to Figure 25A to look up the “FLOW INDEX” needed for the intake and exhaust blowers for the CFM you require. Then, perform the following steps:
1.Open front swinging doors of main unit (by popping front door latches).
2.Throw main power disconnect to the “OFF” position to eliminate risk of injury or death due to electrical shock.
3.Remove five (5) screws holding front ERV door in place (See Figure 27).
4.Remove ERV Control Panel Cover by removing four (4) screws (See Figure 27).
5.Locate two
6.On intake Motor Control Board, observing “GREEN STATUS LIGHT”, turn manual adjust potentiometer “CCW” to increase “FLOW INDEX” or CW to reduce “FLOW INDEX” to
match desired setting.
NOTE: After long pause, the green status light will blink
7.On exhaust Motor Control Board, observing “GREEN STATUS LIGHT”, turn manual adjust potentiometer “CCW” to increase “FLOW INDEX” or CW to reduce “FLOW INDEX” to
match desired setting.
NOTE: Same “GREEN STATUS LIGHT” blink as Step #6.
CHANGING TO FULLY MODULATING MODE
If you want to operate the ERV in fully variable mode (Fig. 25B) (only run at required speed to maintain
1.Open front swinging doors of main unit (by popping front door latches).
2.Throw main power disconnect to the “OFF” position to eliminate risk of injury or death due to electrical shock.
3.Remove ERV Control Panel Cover by removing four (4) screws (See Figure 27).
4.Locate two
5.Pull jumper pins from “M” terminals, and move to “P” terminals (See Figure 28).
6.Connect “+”
7.Follow the directions supplied with the CO2 control to configure the control appropriately.
Manual | |
Page | 41 of 59 |