TABLE 2

ELECTRICAL SPECIFICATIONS

 

 

 

 

Single Circuit

 

 

 

 

Dual Circuit

 

 

 

 

Rated

No. Field

Minimum

Maximum

Field

 

Minimum

Maximum

Field

Ground

Model

Volts, Hertz

Power

Ground

Circuit

External Fuse

Power

Circuit

External Fuse

Power

Wire

and Phase

Circuits

Wire

Ampacity

or Ckt. Breaker

Wire Size

 

Ampacity

or Ckt. Brkr.

Wire Size

 

 

 

 

 

 

Ckt. A

Ckt. B

Ckt. A

Ckt. B

Ckt. A

Ckt. B

Ckt. A

Ckt. B

 

 

 

 

 

 

 

I30H1-A0Z

 

1

22

35

8

10

 

 

 

 

 

 

 

 

A05

230/208-1

1

48

50

8

10

 

 

 

 

 

 

 

 

A10

 

1 or 2

74

80

4

8

48

30

50

30

8

10

10

10

I30H1-B0Z

 

1

17

25

10

10

 

 

 

 

 

 

 

 

B06

230/208-3

1

35

35

8

10

 

 

 

 

 

 

 

 

B09

 

1

44

45

8

10

 

 

 

 

 

 

 

 

I30H1-C0Z

 

1

9

10

14

14

 

 

 

 

 

 

 

 

C06

460-3

1

18

20

12

12

 

 

 

 

 

 

 

 

C09

 

1

22

25

10

10

 

 

 

 

 

 

 

 

I36H1-A0Z

 

1

26

40

8

10

 

 

 

 

 

 

 

 

A05

230/208-1

1

52

60

6

10

 

 

 

 

 

 

 

 

A10

1 or 2

78

80

4

8

26

52

40

60

8

6

10

10

 

1 A15

 

1 or 2

84

90

4

8

26

52

40

60

8

6

10

10

I36H1-B0Z

 

1

22

30

10

10

 

 

 

 

 

 

 

 

B06

230/208-3

1

40

45

8

10

 

 

 

 

 

 

 

 

B09

1

49

50

8

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 B15

 

1

51

60

6

10

 

 

 

 

 

 

 

 

I36H1-C0Z

 

1

11

15

14

14

 

 

 

 

 

 

 

 

C06

460-3

1

20

20

12

12

 

 

 

 

 

 

 

 

C09

1

24

25

10

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 C15

 

1

28

30

10

10

 

 

 

 

 

 

 

 

I42H1-A0Z

 

1

30

45

8

10

 

 

 

 

 

 

 

 

A05

230/208-1

1

56

60

6

10

 

 

 

 

 

 

 

 

A10

1 or 2

82

90

4

8

56

26

60

30

6

10

10

10

 

1 A15

 

1 or 2

82

90

4

8

56

52

60

60

6

6

10

10

I42H1-B0Z

 

1

25

35

8

10

 

 

 

 

 

 

 

 

B06

230/208-3

1

43

50

8

10

 

 

 

 

 

 

 

 

B09

1

52

60

6

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 B15

 

1

52

60

6

10

 

 

 

 

 

 

 

 

I42H1-C0Z

 

1

12

15

14

14

 

 

 

 

 

 

 

 

C06

460-3

1

21

25

10

10

 

 

 

 

 

 

 

 

C09

1

26

30

10

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 C15

 

1

28

30

10

10

 

 

 

 

 

 

 

 

I48H1-A0Z

 

1

34

50

8

10

 

 

 

 

 

 

 

 

A04

 

1

54

60

6

10

 

 

 

 

 

 

 

 

A05

230/208-1

1 or 2

59

70

6

8

35

26

45

30

8

10

10

10

A10

1 or 2

85

90

3

8

35

52

45

60

8

6

10

10

 

1 A15

 

1 or 2

85

90

3

8

35

52

45

60

8

6

10

10

1 A20

 

1 or 2

110

110

2

6

59

52

60

60

6

6

10

10

I48H1-B0Z

 

1

26

35

8

10

 

 

 

 

 

 

 

 

B06

 

1

44

50

8

10

 

 

 

 

 

 

 

 

B09

230/208-3

1

53

60

6

10

 

 

 

 

 

 

 

 

1 B15

 

1

53

60

6

10

 

 

 

 

 

 

 

 

1 B18

 

1

53

60

6

10

 

 

 

 

 

 

 

 

I48H1-C0Z

 

1

15

20

12

12

 

 

 

 

 

 

 

 

C06

 

1

25

30

10

10

 

 

 

 

 

 

 

 

C09

460-3

1

29

30

10

10

 

 

 

 

 

 

 

 

1 C15

 

1

29

30

10

10

 

 

 

 

 

 

 

 

1 C18

 

1

29

30

10

10

 

 

 

 

 

 

 

 

I60H1-A0Z

 

1

44

60

8

10

 

 

 

 

 

 

 

 

A05

 

1 or 2

70

80

4

8

44

26

60

30

8

10

10

10

A10

230/208-1

1 or 2

96

100

3

8

44

52

60

60

8

6

10

10

1 A15

 

1 or 2

96

100

3

8

44

52

60

60

8

6

10

10

1 A20

 

1 or 2

112

120

2

6

60

52

60

60

6

6

10

10

I60H1-B0Z

 

1

31

45

8

10

 

 

 

 

 

 

 

 

B06

 

1

49

60

8

10

 

 

 

 

 

 

 

 

B09

230/208-3

1

58

60

6

10

 

 

 

 

 

 

 

 

1 B15

 

1

58

60

6

10

 

 

 

 

 

 

 

 

1 B18

 

1 or 2

63

70

6

8

31

54

45

60

8

6

10

10

I60H1-C0Z

 

1

15

20

12

12

 

 

 

 

 

 

 

 

C06

 

1

25

30

10

10

 

 

 

 

 

 

 

 

C09

460-3

1

29

30

10

10

 

 

 

 

 

 

 

 

1 C15

 

1

29

30

10

10

 

 

 

 

 

 

 

 

1 C18

 

1

29

30

10

10

 

 

 

 

 

 

 

 

These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electric Code (latest revision), article 310 for power conductor sizing.

Caution: When more than one field power conductor circuit is run through one conduit, the conductors must be derated. Pay special attention to note 8 of table 310 regarding Ampacity Adjustment Factors when more than three conductors are in a raceway.

Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors. Based on 75°C copper wire. All wiring must conform to the National Electrical Code and all local codes. Maximum KW that can operate with heat pump on is 10KW for 1-Phase and 9KW for 3-Phase.

1Represents Electric Heat Only. Electrical Control Circuit will lockout Heat Pump Operation.