Bosch Appliances 24i junior Setting The Gas / Air Ratio, 33.1, 33.3, B 33.4 5.5, Setting the CO2

Models: 28i junior 24i junior

1 62
Download 62 pages 24.83 Kb
Page 53
Image 53
SETTING THE GAS / AIR RATIO

 

 

 

SETTING THE GAS / AIR RATIO

33.1

 

THE SETTING OF THE GAS RATIO MUST BE

 

 

 

CARRIED OUT BY A COMPETENT PERSON.

 

 

 

SETTING OF THE GAS RATIO MUST NOT BE

 

 

 

AT T E M P T E D U N L E S S T H E P E R S O N

 

 

 

C A R R Y I N G O U T T H E C O N V E R S I O N I S

C

EQUIPPED WITH A COMBUSTION ANALYSER

C O N F O R M I N G TO B S 79 2 7 A N D I S

 

 

 

COMPETENT IN ITS USE.

 

 

 

33. Setting the CO2

 

 

Inlet Test NippleNote: When running in the service mode, the

 

 

boiler will operate both the central heating &

 

 

 

 

 

 

 

DHW circuits. This is to allow sufficient time for

 

 

 

the setting procedure. It will be necessary to run

 

 

 

water through the DHW circuit to ensure that

 

 

 

the boiler will not cycle on low heating demands.

33.25.1 Connect manometer to inlet pressure point

on the gas valve.

To adjust the CO2 it will be necessary to first operate the boiler at maximum output.

Press and hold down the service button (A) for 10 seconds until illuminated. The blue power indicator will flash.

 

5.2

Turn central heating control to maximum; the

 

 

boiler will then go to maximum output.

33.3

Note: The control will resume normal operation

after 15 minutes or if the service button is pressed

 

 

for over a second.

 

5.3

Using a flat blade screwdriver set the CO2

 

 

via adjuster (B) using table below.

A

Please note: The flue gas test point can be accessed on the appliance flue elbow by removing cap D

D

+ 33.133. Setting the CO2

B

Inlet Test NippleNote: When running in the service mode, the 33.4

5.5

+

C

 

CO2 settings

Note. CO2 should be measured after 10 minutes

Gas type

CO2 setting

CO2 setting

 

maximum

minimum

 

 

 

Natural gas

9.8% ±0.2

9.2% ±0.2

 

 

 

LPG

11.0% ±0.2

10.5% ±0.2

 

 

 

Check CO is less than 200ppm.

Measure the inlet pressure; it should be no less than 18.5mb for natural gas and 37mb for LPG.

5.4Set the central heating control to minimum. This will make the boiler go to minimum power.

5.5Measure the CO2; it should now be at the figure for minimum output. If not adjust (C) on the gas valve until correct.

Return to maximum and re-check the CO2. If correct press and hold down the service button for 2 seconds; the button will cease to be illuminated and the blue power indicator will be permanently illuminated.

Remove manometer and re-seal inlet pressure point on gas valve.

Fit new plastic sealing cover on to outlet adjuster (B).

Fit white cover over valve adjuster (C) and secure with black security tag.

Remove red arrow from data plate and fit new one in correct position for gas type. Re-assemble and refit boiler case. Re-connect mains electrical supply and check boiler operation as stated in the commissioning section.

Fit new label from kit over existing label on the appliance bottom panel.

SERVICING

& SPARES

52

INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR 24 i junior/28 i junior 8 716 107 336b (11/05)

REPLACEMENT OF PARTS

Page 53
Image 53