| SETTING THE GAS / AIR RATIO |
33.1 |
| ||
THE SETTING OF THE GAS RATIO MUST BE | |||
|
|
| CARRIED OUT BY A COMPETENT PERSON. |
|
|
| SETTING OF THE GAS RATIO MUST NOT BE |
|
|
| AT T E M P T E D U N L E S S T H E P E R S O N |
|
|
| C A R R Y I N G O U T T H E C O N V E R S I O N I S |
C | EQUIPPED WITH A COMBUSTION ANALYSER | ||
C O N F O R M I N G TO B S 79 2 7 A N D I S | |||
|
|
| COMPETENT IN ITS USE. |
|
|
| 33. Setting the CO2 |
|
| Inlet Test Nipple | Note: When running in the service mode, the |
|
| boiler will operate both the central heating & | |
|
| ||
|
| ||
|
|
| DHW circuits. This is to allow sufficient time for |
|
|
| the setting procedure. It will be necessary to run |
|
|
| water through the DHW circuit to ensure that |
|
|
| the boiler will not cycle on low heating demands. |
33.25.1 Connect manometer to inlet pressure point
on the gas valve.
To adjust the CO2 it will be necessary to first operate the boiler at maximum output.
Press and hold down the service button (A) for 10 seconds until illuminated. The blue power indicator will flash.
| 5.2 | Turn central heating control to maximum; the | |
|
| boiler will then go to maximum output. | |
33.3 | Note: The control will resume normal operation | ||
after 15 minutes or if the service button is pressed | |||
| |||
| for over a second. | ||
| 5.3 | Using a flat blade screwdriver set the CO2 | |
|
| via adjuster (B) using table below. |
A
Please note: The flue gas test point can be accessed on the appliance flue elbow by removing cap D
D
+ –
B
33.4
5.5
– | + |
C |
|
CO2 settings
Note. CO2 should be measured after 10 minutes
Gas type | CO2 setting | CO2 setting |
| maximum | minimum |
|
|
|
Natural gas | 9.8% ±0.2 | 9.2% ±0.2 |
|
|
|
LPG | 11.0% ±0.2 | 10.5% ±0.2 |
|
|
|
Check CO is less than 200ppm.
Measure the inlet pressure; it should be no less than 18.5mb for natural gas and 37mb for LPG.
5.4Set the central heating control to minimum. This will make the boiler go to minimum power.
5.5Measure the CO2; it should now be at the figure for minimum output. If not adjust (C) on the gas valve until correct.
Return to maximum and
Remove manometer and
Fit new plastic sealing cover on to outlet adjuster (B).
Fit white cover over valve adjuster (C) and secure with black security tag.
Remove red arrow from data plate and fit new one in correct position for gas type.
Fit new label from kit over existing label on the appliance bottom panel.