Bosch Appliances 24i junior Ignition Sequence, Central Heating Function, Fault Finding Diagrams

Models: 28i junior 24i junior

1 62
Download 62 pages 24.83 Kb
Page 57
Image 57
IGNITION SEQUENCE

INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR 24 i junior/28 i junior 8 716 107 336b (11/05)

POWER SWITCH ON

BLUE LIGHT ON

 

 

 

 

Gas valve OFF.

3 minute wait

 

 

 

Fan overrun

 

 

 

 

 

 

 

30 seconds

 

 

 

 

 

Room

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

thermostat and/or

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

mains

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

programmer ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(or link fitted at

 

 

 

 

 

 

 

 

 

 

Fan to

 

 

 

IGNITION

 

 

GREEN

ST10)

 

 

 

CENTRAL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FLAME

AND

 

 

 

 

 

 

 

 

start

 

 

 

SEQUENCE

 

 

 

 

 

HEATING

 

 

 

 

 

 

 

 

 

 

LIGHT

Facia mounted

 

 

 

DEMAND

 

 

 

 

 

speed.

 

 

 

(see detail)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON

programmer (if fit-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ted) ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AND

 

 

 

 

Diverter valve

 

 

 

 

 

 

 

 

 

 

 

CH control knob

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON

 

 

 

 

in CH position

 

IGNITION SEQUENCE

 

 

 

 

Pump ON.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Over temperature shut- down if water tempera- ture is 5°C above set value.

 

 

 

Fan (& gas)

 

 

 

 

 

 

 

 

 

 

 

 

 

10 second

 

 

modulation

 

 

 

END OF

 

 

 

to achieve

 

 

 

 

stabilisation

 

 

 

 

 

BOILER

 

 

 

set

 

 

 

 

 

 

 

period.

 

 

 

 

 

DEMAND

 

 

 

temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(40-82°C)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CENTRAL HEATING FUNCTION

56

Spark

ignition

4 seconds

NO

 

YES

5th

LOCKOUT

 

 

 

 

attempt?

 

 

 

 

 

 

 

 

 

 

 

FAULT FINDING

& DIAGRAMS

YES

BURNER

LIT?

NO

Stop spark.

Wait

10 seconds

Gas valve

OFF

Pump run 3

minutes

Fan run 30

seconds

CENTRAL HEATING FUNCTION

Page 57
Image 57
Bosch Appliances 24i junior, 28i junior manual Ignition Sequence, Central Heating Function, Fault Finding Diagrams