CONDENSATE CONNECTION
CONDENSATE CONNECTION:
Never terminate or discharge into any open source, including; sink, bath, shower, bidet, toilet etc.
Note: any external condensate pipework should be protected with weather resistant insulation to help prevent freezing.
• Ensure that the condensate drain is 22mm diameter plastic pipe. It must fall at least 50mm per metre towards the outlet.
• An adapter in 22mm pipe is contained in the fitting pack (A) along with sealing washer (B).
INSTALLATION
B
A