INSPECTION AND SERVICE
9Remove burner (L). Remove top baffle (M). Remove baffle (N).
Remove the two hexagon headed screws (O) retaining the access cover (P) on the sump. Access the heat exchanger flue ways by inserting the cleaning brush (7 716 192 312) through the top access hole in the casing (Q). Clean heat exchanger flue ways (R) using the cleaning brush (7 716 192 312) removing any debris from the access point in the sump.
R
P
0
IMPORTANT: IF THE JOINT BETWEEN THE AIR/GAS MANIFOLD AND THE HEAT EXCHANGER IS DISTURBED THE SEALING GASKET MUST BE REPLACED.
Clean around sealing surface on sump and replace access cover (P). Using a suitable container to collect water from syphon connection at the base of the boiler flush heat exchanger with water.
Re-assemble ensuring that the lower baffle
(N)and the top baffle (M) are refitted correctly.
When
Check the syphon unit for blockage before refitting to boiler.
Reassemble and check combustion as stated in the gas conversion section. NOTE: To show the heat exchanger more clearly it has been shown external to the appliance
THE BAFFLES (N) AND (M) MUST BE REFITTED INTO THE HEAT EXCHANGER AS SHOWN IN 9. FAILURE TO DO SO MAY RESULT IN DAMAGE TO THE BOILER
SERVICING | & SPARES |
40
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR 24 i junior/28 i junior 8 716 107 336b (11/05)
INSPECTION AND SERVICE