D7212G

Arming Devices

10.0Arming Devices

10.1Description

Command centers, maintained or momentary contact keyswitches, or a combination of the two are used to arm and disarm areas. The panel may contain up to 4 areas. See Section 2.4.2 Areas and Accounts on page 17 for a description of areas.

10.2Command Center Terminals

The Bosch Security Systems command center is a 4-wire powered device used to arm and disarm areas, annunciate complete system status, initiate system tests, and control many functions of the security system.

The system can supervise up to eight command centers. The panel transmits a serial device trouble report, SDI FAILURE in the Modem IIIa2 format or TROUBLE ZN D in the BFSK format, if it loses communication with a supervised command center. CALL FOR SERVICE appears in any command center with text display capability that loses communication with the panel. SERVC KEYPAD appears at all other command centers connected to the system.

A total of 32 command centers can be connected to the system. The number of supervised command centers, number of areas, and the available power affect the total number of command centers that can be connected to the system. See Command Center in the D7212G Program Entry Guide (P/N: 4998138538) for complete programming details on command center options.

There are five types of command centers available for use with the system:

D1255: 16-character alphanumeric display for general use.

D1256: text display command center with functional keys optimized for local fire alarm control.

D1257: text display command center for fire annunciation.

D1260: Easy-to-read 4-line by 20-character LCD display with eight “Soft” keys for displaying simple selections.

D720: LED display command center appropriate for use as a single area command center with up to eight points. The D1255 and D720 are also available in white (D1255W and D720W) or red (D1255R and D720R) versions.

See the command center’s User’s Guide for operational information.

10.2.1Assigning the command center an address

Switches on the command center assign an address (1 to 8) to the command center. The address determines if the command center is supervised, the command center's scope, and what area the command center is assigned to. See Command Center Assignment in the D7212G Program Entry Guide (P/N: 4998138538) for a complete description of addresses.

Table 12 shows the correct switch setting for each address.

Address

 

 

Switch

 

 

1

2

3

4

5

6

 

Address #1

ON

ON

ON

ON

Encoding

ON

 

 

 

 

 

 

Address #2

OFF

ON

ON

ON

ON

 

 

 

 

 

 

Address #3

ON

OFF

ON

ON

ON

 

 

 

 

 

 

Address #4

OFF

OFF

ON

ON

ON

Tone

 

 

 

 

 

 

Address #5

ON

ON

OFF

ON

ON

 

 

 

 

 

ON/OFF

 

Address #6

OFF

ON

OFF

ON

ON

 

 

 

 

 

 

Address #7

ON

OFF

OFF

ON

ON

 

 

 

 

 

 

Address #8

OFF

OFF

OFF

ON

ON

 

 

 

 

 

 

 

 

Table 12: Command Cneter Address Settings