Bosch Appliances D7212G 3.7Programming the Panel, 3.8Install the Point Chart Label, Installation

Models: D7212G

1 68
Download 68 pages 20.47 Kb
Page 24
Image 24
3.7Programming the Panel

D7212G

Installation

3.6.4Make the Telephone Connections

See Section 6.0 Telephone Connections on page 31. If connecting the panel to a ground start phone system, install a D136 relay, see Section 3.6.3 Install Modules and Relays on page 23.

3.6.5Connect the On-board Points and Command Centers

Connect the on-board points and command center wiring to the system. See Section 7.0 On-board Points on page 35 and Section 10.0 Arming Devices on page 49 for instructions.

3.6.6Power Up

Reconnect the battery, and then plug in the transformer. Remember - the buzzer sounds for two seconds when the panel is first powered up.

Leave the reset pin locked down for now.

Yellow Charging Status LED doesn’t go out: If the yellow charging status LED doesn’t go out within five minutes of powering up the panel, the battery may be deeply discharged, or too many powered devices have been connected to the panel. Combined continuous current draw for Terminals 3, 8, and 32 cannot exceed 1.4 A. See Section 5.0 Power Outputs on page 29 for help.

3.7Programming the Panel

If a program hasn’t been created for the panel, review the D7212G Program Entry Guide (P/N: 4998138538). Check to be certain all the required accessory modules to be installed for desired features are available. The reset pin must be in the locked position to copy or send information to and from the panel.

Use the D5200 Programmer or the Remote Account Manager (RAM IV) to load a custom program into the panel.

Move the reset pin to the normal position. See Figure 4 on page 22. The panel transmits reboot and battery reports to the receiver if programmed for reporting.

3.8Install the Point Chart Label

Bosch Security Systems recommends the 7000/9000 Series Point Chart Label (P/N: 79-06660-000) provided in the literature pack be filled out and installed on the inside of the enclosure door for all systems.

Point chart label required for fire systems with verification points: The point chart label must be installed for fire or combined fire/burglary systems using verification points.

Use the D7212G Program Record Sheet (P/N: 4998138542) to gather the information needed to fill out the point chart. Install the label on the enclosure door as shown in Figure 2 on page 21. To avoid smearing the entries on the chart, use the label's peel off backing to press the label in place.

3.9Testing the System

After finishing the installation and programming of the panel, make a complete functional test of the system. Test the panel and all devices for proper operation. Test after first programming the panel and after any subsequent programming session.

Service Walk Test: Use the service walk test at a panel wide command center to perform a complete test of the panel. The service walk test function is similar to the ordinary walk test function, with the additional ability to display points that are not properly programmed.

If a device is tested and the panel doesn’t respond, there may be a problem with the device, the wiring, the POPIT ID setting, or the programming for the point. If the switches on a POPIT are set incorrectly, it may create both a missing and extra point conditions.

See the D9412G/D7412G/D7212G Installation and Troubleshooting Quick Reference Guide (P/N: 43700) for complete service walk test instructions.

Clear after test: To clear the event memory and report buffer, momentarily close the reset pin. Events stored in the panel's event log are not cleared.

D7212G Operation and Installation Guide

4998138544C

Page 24

© 2003 Bosch Security Systems

Page 24
Image 24
Bosch Appliances D7212G 3.7Programming the Panel, 3.8Install the Point Chart Label, 3.9Testing the System, Installation