Telephone Connections

 

 

 

D7212G

 

 

 

Overview

 

 

 

 

 

Telephone Connections

Telephone Line

 

RJ31X or RJ38X jack can be interfaced with the

 

 

Connection

 

panels.

 

 

 

 

Supervision supplied by the panel.

 

Battery

Discharge Cycle

13.9 VDC

Charging float level

 

Discharge/Recharge

 

13.8 VDC

Charging Status LED on

 

Schedule

 

12.1 VDC

Low Battery & AC Fail reports if programmed,

 

 

 

 

Low Battery LED on

 

 

 

10.2 VDC

Battery load shed (processing functions

 

 

 

 

continue if AC is present)

 

 

Recharge Cycle

AC ON

Load shed relay resets battery charging begins,

 

 

 

 

Battery Trouble and AC Restoral reports sent.

 

 

 

13.7 VDC

Battery Restoral report sent, Low Battery LED

 

 

 

13.9 VDC

off

 

 

 

 

Charging Status LED off, battery float charged

 

Environmental

Temperature:

+32°F to +122°F (0°C to +50°C)

 

 

Relative Humidity:

5% to 85% @ +86°F (+30°C) non-condensing

 

 

 

 

Arming Stations

D1255 Command Center; D1256 Fire Command Center; D1257 Fire Alarm

 

 

Annunciator; D1260 Alpha V Command Center; D720 Command Center; Keyswitch

 

Point Thresholds

On board Points

Open

Greater than 3.7 VDC, but less than 5.0 VDC.

 

 

1 to 8

Normal

Greater than 2.0 VDC, but less than 3.0 VDC.

 

 

 

Short

Greater than 0.0 VDC, but less than 1.3 VDC.

 

Compatible Enclosures

D8103 Universal Enclosure, D8109 Fire Enclosure, D8108A Attack Resistant Enclosure

 