12″ MIN
12″ MIN
VENT PIPE
VENT
HORIZONTAL TO ROOF | HORIZONTAL TO SIDEWALL |
| |
| VENT PIPE |
| |
| 12″ MIN |
12″ MIN | VENT PIPE |
| |
VERTICAL TO ROOF | VERTICAL TO SIDEWALL |
NOTE: A 12 In. minimum offset pipe section is recommended with short (5 to 8 ft) vent systems. This recommendation is to reduce excessive condensate droplets from exiting the vent pipe.
A96230
Fig. 34—Short Vent (5 to 8 Ft) System
d.Install pipe support
e.Insert
NOTE: A
f. Install casing hole filler cap
g. Drill a
h.Install a
NOTE: DO NOT OVERTIGHTEN SCREW. Breakage of intake housing or fitting may cause air leakage to occur.
NOTE: Do not attach
FITTING
The
NOTE: DO NOT OVERTIGHTEN SCREW. Breakage of intake housing or fitting may cause air leakage to occur.
A plugged drain connection has been provided on this fitting for use when moisture is found in
NOTE: Moisture in
If use of this drain connection is desired, drill out fitting’s tap plug with a
2.Attach vent pipe as follows:
a.Determine location of vent pipe connection to inducer housing as shown in Fig. 33 for application.