Bryant 340MAV AirIntake Housing Plug Fitting Drain, Maximumallowable Pipe Length Ft Continued

Models: 340MAV

1 48
Download 48 pages 30.25 Kb
Page 29
Image 29
Fig. 35—Air Intake Housing Plug Fitting Drain

TABLE 7—MAXIMUM ALLOWABLE PIPE LENGTH (FT) (CONTINUED)

ALTITUDE (FT)

UNIT SIZE

TERMINATION

PIPE DIA

 

 

NUMBER OF 90° ELBOWS

 

TYPE

(IN.)*

1

2

 

3

4

5

6

 

 

 

 

024040

2 Pipe or 2-in

1-1/2

46

41

 

36

31

29

24

 

036040

Concentric

2

62

60

 

58

56

55

53

 

024060

2 Pipe or 2-in

1-1/2

11

6

 

NA

NA

NA

NA

 

036060

 

 

 

 

 

 

 

 

 

Concentric

2

49

44

 

42

37

35

34

 

048060

 

 

 

 

 

036080

2 Pipe or 2-in

2

33

28

 

17

12

10

NA

8001 to 9000‡

048080

 

 

 

 

 

 

 

 

Concentric

2-1/2

62

60

 

58

56

55

53

 

060080

 

 

 

048100

2 Pipe or 3-in

2-1/2

23

15

 

7

5

NA

NA

 

060100

Concentric

3

59

54

 

49

44

39

34

 

060120

2 Pipe or 3-in.

3† no disk

10

NA

 

NA

NA

NA

NA

 

Concentric

4† no disk

35

30

 

25

20

15

10

 

 

 

 

060140

 

 

 

NA

 

 

 

 

 

ALTITUDE (FT)

UNIT SIZE

TERMINATION

PIPE DIA

 

 

NUMBER OF 90° ELBOWS

 

TYPE

(IN.)*

1

2

 

3

4

5

6

 

 

 

 

024040

2 Pipe or 2-in

1-1/2

42

37

 

32

27

25

20

 

036040

Concentric

2

57

55

 

53

51

49

47

 

024060

2 Pipe or 2-in

 

 

 

 

 

 

 

 

 

036060

2

45

40

 

38

33

31

29

 

Concentric

 

 

048060

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

036080

2 Pipe or 2-in

2

30

25

 

14

9

7

NA

9001 to 10,000‡

048080

 

 

 

 

 

 

 

 

Concentric

2-1/2

57

55

 

53

51

49

47

 

060080

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

048100

2 Pipe or 3-in

2-1/2

21

13

 

5

NA

NA

NA

 

060100

Concentric

3

54

49

 

44

39

34

29

 

 

 

 

 

 

 

 

 

 

 

 

060120

2 Pipe or 3-in.

4† no disk

10

5

 

NA

NA

NA

NA

 

Concentric

 

 

 

 

 

 

 

 

 

 

 

 

060140

 

 

 

NA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Disk usage-Unless otherwise specified, use perforated disk assembly (factory-supplied in loose parts bag). If one disk is stated, separate 2 halves of perforated disk assembly and use shouldered disk half. When using shouldered disk half, install screen side toward inlet box.

†Wide radius elbow.

‡Vent sizing for Canadian installations over 4500 ft (1370 m) above sea level are subject to acceptance by the local authorities having jurisdiction. NA-Not Allowed; pressure switch will not make.

NOTES:

1.Do not use pipe size greater than those specified in table or incomplete combustion, flame disturbance, or flame sense lockout may occur.

2.Size both the combustion-air and vent pipe independently, then use the larger diameter for both pipes.

3.Assume two 45° elbows equal one 90° elbow. Long radius elbows are desirable and may be required in some cases.

4.Elbows and pipe sections within the furnace casing and at the vent termination should not be included in vent length or elbow count.

5.The minimum pipe length is 5 ft for all applications.

6.Use 3-in. diameter vent termination kit for installations requiring 4-in diameter pipe.

COMBUSTION – AIR

INTAKE HOUSING

3/8" ID TUBE

BURNER

 

BOX

WARNING: Inducer housing outlet cap must be in- stalled and fully seated against inducer housing. Clamp must be tightened to prevent any condensate leakage. Failure to follow this warning could result in electrical shock, fire, personal injury, or death.

3/16"

DRILL

COMBUSTION – AIR PIPE

c. Install pipe support (factory-supplied in loose parts bag)

into selected furnace casing vent pipe hole. Pipe support

TRAP

4

MIN

should be positioned at bottom of casing hole.

WARNING: Vent pipe must be installed and fully seated against inducer housing internal stop. Clamp must

TO OPEN

DRAIN

A93035

Fig. 35—Air Intake Housing Plug Fitting Drain

b.Reposition elastometric (rubber) inducer housing outlet cap and clamp to appropriate unused inducer housing connection. Tighten clamp.

—29—

be tightened to prevent any condensate leakage. Failure to follow this warning could result in electrical shock, fire, personal injury, or death.

NOTE: A 2-in. diameter pipe must be used within the furnace casing. Make all pipe diameter transitions outside furnace casing.

d. Be certain that mating surfaces of inducer housing connection, elastomeric coupling, and 2-in. diameter vent pipe are clean and dry. Assemble the elastomeric (rubber) vent coupling (with 2 loose clamps) onto inducer housing connection. Insert the 2-in. diameter vent pipe through the elastomeric (rubber) coupling and

Page 29
Image 29
Bryant 340MAV instruction manual AirIntake Housing Plug Fitting Drain, Maximumallowable Pipe Length Ft Continued