TABLE
ALTITUDE (FT) | UNIT SIZE | TERMINATION | PIPE DIA |
|
| NUMBER OF 90° ELBOWS |
| |||
TYPE | (IN.)* | 1 | 2 |
| 3 | 4 | 5 | 6 | ||
|
|
| ||||||||
| 024040 | 2 Pipe or | 46 | 41 |
| 36 | 31 | 29 | 24 | |
| 036040 | Concentric | 2 | 62 | 60 |
| 58 | 56 | 55 | 53 |
| 024060 | 2 Pipe or | 11 | 6 |
| NA | NA | NA | NA | |
| 036060 |
|
|
|
|
|
|
|
| |
| Concentric | 2 | 49 | 44 |
| 42 | 37 | 35 | 34 | |
| 048060 |
| ||||||||
|
|
| ||||||||
| 036080 | 2 Pipe or | 2 | 33 | 28 |
| 17 | 12 | 10 | NA |
8001 to 9000‡ | 048080 |
|
|
|
|
|
|
|
| |
Concentric | 62 | 60 |
| 58 | 56 | 55 | 53 | |||
| 060080 |
|
| |||||||
| 048100 | 2 Pipe or | 23 | 15 |
| 7 | 5 | NA | NA | |
| 060100 | Concentric | 3 | 59 | 54 |
| 49 | 44 | 39 | 34 |
| 060120 | 2 Pipe or | 3† no disk | 10 | NA |
| NA | NA | NA | NA |
| Concentric | 4† no disk | 35 | 30 |
| 25 | 20 | 15 | 10 | |
|
|
| ||||||||
| 060140 |
|
|
| NA |
|
|
|
|
|
ALTITUDE (FT) | UNIT SIZE | TERMINATION | PIPE DIA |
|
| NUMBER OF 90° ELBOWS |
| |||
TYPE | (IN.)* | 1 | 2 |
| 3 | 4 | 5 | 6 | ||
|
|
| ||||||||
| 024040 | 2 Pipe or | 42 | 37 |
| 32 | 27 | 25 | 20 | |
| 036040 | Concentric | 2 | 57 | 55 |
| 53 | 51 | 49 | 47 |
| 024060 | 2 Pipe or |
|
|
|
|
|
|
|
|
| 036060 | 2 | 45 | 40 |
| 38 | 33 | 31 | 29 | |
| Concentric |
| ||||||||
| 048060 |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
| 036080 | 2 Pipe or | 2 | 30 | 25 |
| 14 | 9 | 7 | NA |
9001 to 10,000‡ | 048080 |
|
|
|
|
|
|
|
| |
Concentric | 57 | 55 |
| 53 | 51 | 49 | 47 | |||
| 060080 |
| ||||||||
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
| 048100 | 2 Pipe or | 21 | 13 |
| 5 | NA | NA | NA | |
| 060100 | Concentric | 3 | 54 | 49 |
| 44 | 39 | 34 | 29 |
|
|
|
|
|
|
|
|
|
|
|
| 060120 | 2 Pipe or | 4† no disk | 10 | 5 |
| NA | NA | NA | NA |
| Concentric |
| ||||||||
|
|
|
|
|
|
|
|
|
| |
| 060140 |
|
|
| NA |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Disk
†Wide radius elbow.
‡Vent sizing for Canadian installations over 4500 ft (1370 m) above sea level are subject to acceptance by the local authorities having jurisdiction.
NOTES:
1.Do not use pipe size greater than those specified in table or incomplete combustion, flame disturbance, or flame sense lockout may occur.
2.Size both the
3.Assume two 45° elbows equal one 90° elbow. Long radius elbows are desirable and may be required in some cases.
4.Elbows and pipe sections within the furnace casing and at the vent termination should not be included in vent length or elbow count.
5.The minimum pipe length is 5 ft for all applications.
6.Use
COMBUSTION – AIR
INTAKE HOUSING
3/8" ID TUBE | BURNER |
| BOX |
WARNING: Inducer housing outlet cap must be in- stalled and fully seated against inducer housing. Clamp must be tightened to prevent any condensate leakage. Failure to follow this warning could result in electrical shock, fire, personal injury, or death.
3/16"
DRILL
COMBUSTION – AIR PIPE
c. Install pipe support |
into selected furnace casing vent pipe hole. Pipe support |
TRAP
4″
MIN
should be positioned at bottom of casing hole. |
WARNING: Vent pipe must be installed and fully seated against inducer housing internal stop. Clamp must
TO OPEN
DRAIN
A93035
Fig. 35—Air Intake Housing Plug Fitting Drain
b.Reposition elastometric (rubber) inducer housing outlet cap and clamp to appropriate unused inducer housing connection. Tighten clamp.
be tightened to prevent any condensate leakage. Failure to follow this warning could result in electrical shock, fire, personal injury, or death.
NOTE: A
d. Be certain that mating surfaces of inducer housing connection, elastomeric coupling, and