TABLE 9—MODEL 340MAV ORIFICE SIZE AND MANIFOLD PRESSURE FOR CORRECT INPUT

(Continued)

 

 

 

 

FOR USE WITH 040 THROUGH 120 SIZE FURNACES ONLY

 

 

 

 

 

 

 

(TABULATED DATA BASED ON 20,000 BTUH PER BURNER, DERATED 2% FOR EACH 1000 FT ABOVE SEA LEVEL)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ALTITUDE

AVG GAS

 

 

 

 

 

SPECIFIC GRAVITY OF NATURAL GAS

 

 

 

 

 

HEAT VALUE

 

0.58

 

0.60

 

0.62

 

0.64

 

 

0.66

 

 

RANGE

 

 

 

 

 

 

 

 

(FT)

AT ALTITUDE

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

 

Orifice

 

Manifold

 

 

(BTU/CU FT)

 

 

 

 

 

 

 

 

 

No.

 

Pressure

No.

 

Pressure

No.

 

Pressure

No.

 

Pressure

 

No.

 

Pressure

 

 

 

625

43

 

3.8

42

 

3.3

42

 

3.4

42

 

3.5

 

42

 

3.6

 

 

 

650

43

 

3.5

43

 

3.7

43

 

3.8

42

 

3.2

 

42

 

3.3

Only

 

7001

675

44

 

3.8

43

 

3.4

43

 

3.5

43

 

3.6

 

43

 

3.7

 

 

700

44

 

3.5

44

 

3.6

44

 

3.8

43

 

3.4

 

43

 

3.5

 

 

 

 

 

 

 

 

 

U.S.A.

 

to

725

44

 

3.3

44

 

3.4

44

 

3.5

44

 

3.6

 

44

 

3.7

 

8000

775

45

 

3.5

45

 

3.6

45

 

3.7

45

 

3.8

 

44

 

3.3

 

 

 

750

45

 

3.7

45

 

3.8

44

 

3.3

44

 

3.4

 

44

 

3.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

800

45

 

3.3

45

 

3.4

45

 

3.5

45

 

3.6

 

45

 

3.7

 

 

15%

825

45

 

3.1

45

 

3.2

45

 

3.3

45

 

3.4

 

45

 

3.5

 

 

derate

850

45

 

2.9

45

 

3.0

45

 

3.1

45

 

3.2

 

45

 

3.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ALTITUDE

AVG GAS

 

 

 

 

 

SPECIFIC GRAVITY OF NATURAL GAS

 

 

 

 

 

HEAT VALUE

 

0.58

 

0.60

 

0.62

 

0.64

 

 

0.66

 

 

RANGE

 

 

 

 

 

 

 

 

(FT)

AT ALTITUDE

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

 

Orifice

 

Manifold

 

 

(BTU/CU FT)

 

 

 

 

 

 

 

 

 

No.

 

Pressure

No.

 

Pressure

No.

 

Pressure

No.

 

Pressure

 

No.

 

Pressure

 

 

 

600

43

 

3.8

42

 

3.3

42

 

3.4

42

 

3.5

 

42

 

3.6

 

 

8001

625

43

 

3.5

43

 

3.6

43

 

3.8

42

 

3.2

 

42

 

3.3

Only

 

 

650

44

 

3.7

43

 

3.4

43

 

3.5

43

 

3.6

 

43

 

3.7

 

to

675

44

 

3.5

44

 

3.6

44

 

3.7

44

 

3.8

 

43

 

3.4

 

 

 

 

 

 

 

 

U.S.A.

 

 

700

44

 

3.2

44

 

3.3

44

 

3.4

44

 

3.6

 

44

 

3.7

 

9000

725

45

 

3.6

45

 

3.8

44

 

3.2

44

 

3.3

 

44

 

3.4

 

 

 

 

 

 

 

 

 

 

 

750

45

 

3.4

45

 

3.5

45

 

3.6

45

 

3.8

 

44

 

3.2

 

 

17%

775

45

 

3.2

45

 

3.3

45

 

3.4

45

 

3.5

 

45

 

3.6

 

 

derate

800

45

 

3.0

45

 

3.1

45

 

3.2

45

 

3.3

 

45

 

3.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ALTITUDE

AVG GAS

 

 

 

 

 

SPECIFIC GRAVITY OF NATURAL GAS

 

 

 

 

 

HEAT VALUE

 

0.58

 

0.60

 

0.62

 

0.64

 

 

0.66

 

 

RANGE

 

 

 

 

 

 

 

 

(FT)

AT ALTITUDE

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

 

Orifice

 

Manifold

 

 

(BTU/CU FT)

 

 

 

 

 

 

 

 

 

No.

 

Pressure

No.

 

Pressure

No.

 

Pressure

No.

 

Pressure

 

No.

 

Pressure

 

 

 

575

43

 

3.8

42

 

3.2

42

 

3.3

42

 

3.5

 

42

 

3.6

 

 

9001

600

43

 

3.5

43

 

3.6

43

 

3.7

42

 

3.2

 

42

 

3.3

Only

 

 

625

44

 

3.7

44

 

3.8

43

 

3.5

43

 

3.6

 

43

 

3.7

 

to

650

44

 

3.4

44

 

3.5

44

 

3.7

44

 

3.8

 

43

 

3.4

 

 

 

 

 

 

 

 

U.S.A.

 

 

675

45

 

3.8

44

 

3.3

44

 

3.4

44

 

3.5

 

44

 

3.6

 

10,000

700

45

 

3.6

45

 

3.7

45

 

3.8

44

 

3.3

 

44

 

3.4

 

 

 

 

 

 

 

 

 

 

 

725

45

 

3.3

45

 

3.4

45

 

3.6

45

 

3.7

 

45

 

3.8

 

 

19%

750

45

 

3.1

45

 

3.2

45

 

3.3

45

 

3.4

 

45

 

3.5

 

 

derate

775

45

 

2.9

45

 

3.0

45

 

3.1

45

 

3.2

 

45

 

3.3

*Orifice numbers shown in BOLD are factory installed.

Percents of derate are based on midpoints of U.S. altitude ranges.