and Canada. In Canada construct all combustion-air and vent pipes for this unit of CSA or ULC listed schedule-40 PVC, PVC-DWV or ABS-DWV pipe and pipe cement. SDR pipe is NOT approved in Canada.

See Table 7 for maximum pipe lengths and Fig. 36, 37, 38, 39, and 40 for exterior piping arrangements.

NOTE: Furnace combustion-air and vent pipe connections are sized for 2-in. pipe. Any pipe size change should be made outside furnace casing in vertical pipe. (See Fig. 32.) This allows proper drainage of vent condensate.

Combustion-air and vent pipes must terminate together in same atmospheric pressure zone, either through roof or sidewall (roof termination preferred), using accessory termination kit. See Table 5 for required clearances.

Furnace combustion-air and vent pipe connections must be at- tached as shown in Fig. 27. Combustion-air intake plug fitting and inducer housing alternate vent cap may need to be relocated in some applications.

NOTE: Slope combustion-air and vent pipes a minimum of 1/4 in. per linear ft with no sags between hangers.

CAUTION: When combustion-air pipe is installed above a suspended ceiling, pipe must be insulated with 3/8-in. thick Armaflex-type insulation. Combustion-air pipe should also be insulated when it passes through warm, humid space.

CAUTION: When vent pipe is exposed to temperatures below freezing, such as when it passes through an

unheated space or when a chimney is used as a raceway, pipe must be insulated as shown in Table 8 with Armaflex-type insulation. Failure to follow this caution will result in intermittent unit operation.

An abandoned masonry chimney may be used as a raceway for properly insulated and supported combustion-air and vent pipes. Each furnace must have its own set of combustion-air and vent pipes and be terminated individually, as shown in Fig. 42.

Other gas appliances with their own venting system may also use the abandoned chimney as a raceway providing it is permitted by local code, the current edition of the NFGC or NSCNGPIC, and the vent or liner manufacturer’s Installation Instructions. Care must be taken to prevent the exhaust gases from one appliance from contaminating the combustion air of other gas appliances.

CAUTION: Combustion air must not be taken from inside structure because inside air is frequently contami- nated by halogens, which include fluorides, chlorides, bromides, and iodides. These elements are found in aerosols, detergents, bleaches, cleaning solvents, salts, air fresheners, adhesives, paint, and other household prod- ucts. Locate combustion-air inlet as far as possible from swimming pool and swimming pool pump house.

Excessive exposure to contaminated combustion air will result in safety and performance related problems.

WARNING: Solvent cements are combustible. Keep away from heat, sparks, and open flame. Use only in well ventilated areas. Avoid breathing in vapor or allowing contact with skin or eyes. Failure to follow this warning could result in fire, property damage, personal injury, or death.

WARNING: All combustion-air and vent pipes must be airtight and watertight. Pipes must also terminate exactly as shown in Fig. 36, 37, 38, 39, or 40. Failure to follow this warning could result in property damage, personal injury, or death.

TABLE 5—COMBUSTION-AIR AND VENT PIPE

TERMINATION CLEARANCES

LOCATION

CLEARANCE (FT)

U.S.A.

Canada

 

 

 

 

Above grade level or above antici-

1

1†

pated snow depth

 

 

Water heater/Dryer vent

See Note 5

See Note 5

From plumbing vent stack

3

3

From any mechanical fresh air intake

See Note 4

6

For furnaces with an input capacity

 

 

equal to or less than 100,000

 

 

Btuh—from any non-mechanical air

1

1

supply (windows or doors which can

 

 

be opened) or combustion-air opening

 

 

For furnaces with an input capacity

 

 

greater than 100,000 Btuh-from any

 

 

nonmechanical air supply (windows or

1

3

doors which can be opened) or

 

 

combustion-air opening

 

 

From service regulator vent, electric

See Note 6

See Note 6

and gas meters, and relief equipment

 

 

Above grade when adjacent to public

 

 

NOT IN HORIZONTAL SECTION

FURNACE

PIPE DIAMETER

TRANSITION IN

VERTICAL SECTION

A93034

walkway

Note 3

Note 3

 

 

† 18 in. above roof surface in Canada.

NOTES:

1. If installing 2 adjacent Furnaces, refer to Multiventing and Vent Terminations

section for proper vent configurations.

2. When locating combustion-air and vent terminations, consideration must be

given to prevailing winds, location, and other conditions which may cause

recirculation of the appliance’s own flue products or the flue products of

adjacent vents. Recirculation can cause poor combustion, inlet condensate

problems, and accelerated corrosion of heat exchangers.

3. Vent termination can not terminate less than 2 ft horizontal and 7 ft above

public walkway or where condensate vapor or droplets may be a hazard.

4. Vent termination must be at least 3 feet above any forced draft inlets within

10 feet horizontal. Vent termination must be at least 3 feet horizontal from

other direct vent appliances intake unless otherwise specified by manufac-

turer.

5. 3 ft radius of furnace air-intake terminal and 1 ft horizontally from vertical

Fig. 32—Combustion-Air and Vent Pipe Diameter

Transition Location and Elbow Configuration

centerline of furnace air-intake terminal.

6. Above a meter/regulator within 3 feet horizontally of vertical centerline of

meter/regulator vent outlet to a maximum vertical distance of 15 feet.

—24—

Page 24
Image 24
Bryant 340MAV instruction manual COMBUSTION-AIR and Vent Pipe Termination Clearances, Clearance FT

340MAV specifications

The Bryant 340MAV is a standout model in the Bryant lineup, designed to provide exceptional comfort, efficiency, and performance for residential heating and cooling needs. This unit offers a perfect blend of innovative technology and user-friendly features, making it an ideal choice for homeowners seeking reliability and quality.

One of the defining characteristics of the Bryant 340MAV is its impressive efficiency rating. With a SEER (Seasonal Energy Efficiency Ratio) of up to 18, this model ensures that homeowners can enjoy effective cooling during the summer months while minimizing energy consumption. Similarly, the heating efficiency is notable, with a high AFUE (Annual Fuel Utilization Efficiency) rating. This makes the 340MAV an environmentally friendly option that also promotes cost savings on energy bills.

The 340MAV incorporates advanced technologies that enhance its performance. One such technology is the variable-speed compressor, which allows the system to adjust its output based on the demands of the home. This means that the unit operates more quietly and reduces energy usage by matching the cooling or heating output required. Additionally, the two-stage heating capability provides more consistent temperatures and improved comfort throughout the space.

Operating noise is a crucial factor in residential HVAC systems, and the Bryant 340MAV is designed with this in mind. Engineered for quiet operation, the unit features a sound-dampening design, including an insulated cabinet and a specially designed compressor that minimizes noise levels. Homeowners can enjoy a comfortable indoor climate without the disruptive racket often associated with traditional systems.

Furthermore, the Bryant 340MAV is equipped with a durable all-aluminum coil, which improves heat transfer efficiency while also being resistant to corrosion. This characteristic contributes to the longevity of the unit, ensuring that it can withstand various environmental factors without compromising performance.

Another key feature is the advanced control options that the Bryant 340MAV offers. Integration with smart thermostats allows homeowners to monitor and adjust their HVAC system remotely, ensuring optimal comfort at all times. Additionally, the system is compatible with Bryant's Perfect Airâ„¢ filtration system, enhancing indoor air quality by reducing pollutants and allergens.

In summary, the Bryant 340MAV is a high-efficiency heating and cooling solution that brings together cutting-edge technology, quiet operation, and user-friendly features. With its focus on comfort and energy savings, it stands out as a prime choice for homeowners looking to invest in a reliable HVAC system.