CO2 Sensor Configuration
The CO2 sensor has preset standard voltage settings that can be selected anytime after the sensor is powered up. See Table 5.
Use setting 1 or 2 for Bryant equipment. See Table 5.
1.Press Clear and Mode buttons. Hold at least 5 sec- onds until the sensor enters the Edit mode.
2.Press Mode twice. The STDSET Menu will appear.
3.Use the Up/Down button to select the preset number. See Table 5.
4.Press Enter to lock in the selection.
5.Press Mode to exit and resume normal operation.
The custom settings of the CO2 sensor can be changed any- time after the sensor is energized. Follow the steps below to change the
1.Press Clear and Mode buttons. Hold at least 5 sec- onds until the sensor enters the Edit mode.
2.Press Mode twice. The STDSET Menu will appear.
3.Use the Up/Down button to toggle to the NONSTD menu and press Enter.
4.Use the Up/Down button to toggle through each of the nine variables, starting with Altitude, until the desired setting is reached.
5.Press Mode to move through the variables.
6.Press Enter to lock in the selection, then press Mode to continue to the next variable.
Dehumidification of Fresh Air with DCV Control
Information from ASHRAE indicates that the largest humid- ity load on any zone is the fresh air introduced. For some applications, a device such as an energy recovery unit is added to reduce the moisture content of the fresh air being brought into the building when the enthalpy is high. In most cases, the normal heating and cooling processes are more than adequate to remove the humidity loads for most com- mercial applications.
If normal rooftop heating and cooling operation is not ade- quate for the outdoor humidity level, an energy recovery unit and/or a dehumidification option should be considered.
Table 5 — CO2 Sensor Standard Settings
|
|
| VENTILATION | ANALOG | CO2 | OPTIONAL | RELAY | |
SETTING | EQUIPMENT | OUTPUT | RATE | CONTROL RANGE | RELAY SETPOINT | HYSTERESIS | ||
OUTPUT | ||||||||
|
|
| (cfm/Person) | (ppm) | (ppm) | (ppm) | ||
|
|
|
| |||||
1 |
| Proportional | Any | 1000 | 50 | |||
| ||||||||
|
|
|
|
|
|
| ||
2 | Interface w/Standard | Proportional | Any | 1000 | 50 | |||
Building Control System | ||||||||
|
|
|
|
|
| |||
3 |
| Exponential | Any | 1100 | 50 | |||
| ||||||||
|
|
|
|
|
|
| ||
4 |
| Proportional | 15 | 1100 | 50 | |||
| ||||||||
|
|
|
|
|
|
| ||
5 |
| Proportional | 20 | 0- 900 | 900 | 50 | ||
| ||||||||
| Economizer |
|
|
|
|
| ||
6 | Exponential | 15 | 1100 | 50 | ||||
| ||||||||
| ||||||||
|
|
|
|
|
|
| ||
7 |
| Exponential | 20 | 0- 900 | 900 | 50 | ||
| ||||||||
|
|
|
|
|
|
| ||
8 | Health & Safety | Proportional | — | 5000 | 500 | |||
|
|
|
|
|
|
| ||
9 | Parking/Air Intakes/ | Proportional | — | 700 | 50 | |||
Loading Docks | ||||||||
|
|
|
|
|
|
LEGEND
ppm — Parts Per Million