Bryant 558F installation instructions CO2 Sensor Standard Settings

Models: 558F

1 70
Download 70 pages 22.19 Kb
Page 30
Image 30

CO2 Sensor Configuration

The CO2 sensor has preset standard voltage settings that can be selected anytime after the sensor is powered up. See Table 5.

Use setting 1 or 2 for Bryant equipment. See Table 5.

1.Press Clear and Mode buttons. Hold at least 5 sec- onds until the sensor enters the Edit mode.

2.Press Mode twice. The STDSET Menu will appear.

3.Use the Up/Down button to select the preset number. See Table 5.

4.Press Enter to lock in the selection.

5.Press Mode to exit and resume normal operation.

The custom settings of the CO2 sensor can be changed any- time after the sensor is energized. Follow the steps below to change the non-standard settings:

1.Press Clear and Mode buttons. Hold at least 5 sec- onds until the sensor enters the Edit mode.

2.Press Mode twice. The STDSET Menu will appear.

3.Use the Up/Down button to toggle to the NONSTD menu and press Enter.

4.Use the Up/Down button to toggle through each of the nine variables, starting with Altitude, until the desired setting is reached.

5.Press Mode to move through the variables.

6.Press Enter to lock in the selection, then press Mode to continue to the next variable.

Dehumidification of Fresh Air with DCV Control

Information from ASHRAE indicates that the largest humid- ity load on any zone is the fresh air introduced. For some applications, a device such as an energy recovery unit is added to reduce the moisture content of the fresh air being brought into the building when the enthalpy is high. In most cases, the normal heating and cooling processes are more than adequate to remove the humidity loads for most com- mercial applications.

If normal rooftop heating and cooling operation is not ade- quate for the outdoor humidity level, an energy recovery unit and/or a dehumidification option should be considered.

Table 5 — CO2 Sensor Standard Settings

 

 

 

VENTILATION

ANALOG

CO2

OPTIONAL

RELAY

SETTING

EQUIPMENT

OUTPUT

RATE

CONTROL RANGE

RELAY SETPOINT

HYSTERESIS

OUTPUT

 

 

 

(cfm/Person)

(ppm)

(ppm)

(ppm)

 

 

 

 

1

 

Proportional

Any

0-10V

0-2000

1000

50

 

4-20 mA

 

 

 

 

 

 

 

2

Interface w/Standard

Proportional

Any

2-10V

0-2000

1000

50

Building Control System

7-20 mA

 

 

 

 

 

 

3

 

Exponential

Any

0-10V

0-2000

1100

50

 

4-20 mA

 

 

 

 

 

 

 

4

 

Proportional

15

0-10V

0-1100

1100

50

 

4-20 mA

 

 

 

 

 

 

 

5

 

Proportional

20

0-10V

0- 900

900

50

 

4-20 mA

 

Economizer

 

 

 

 

 

6

Exponential

15

0-10V

0-1100

1100

50

 

 

4-20 mA

 

 

 

 

 

 

 

7

 

Exponential

20

0-10V

0- 900

900

50

 

4-20 mA

 

 

 

 

 

 

 

8

Health & Safety

Proportional

0-10V

0-9999

5000

500

4-20 mA

 

 

 

 

 

 

 

9

Parking/Air Intakes/

Proportional

0-10V

0-2000

700

50

Loading Docks

4-20 mA

 

 

 

 

 

 

LEGEND

ppm — Parts Per Million

30

Page 30
Image 30
Bryant 558F installation instructions CO2 Sensor Standard Settings