Bryant 558F installation instructions

Models: 558F

1 70
Download 70 pages 22.19 Kb
Page 47
Image 47

Table 23 — Fan Performance 558F102,103 — Horizontal Discharge Units; Standard Motor (Belt Drive)*

AIRFLOW

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

0.2

 

 

0.4

 

 

0.6

 

 

0.8

 

 

1.0

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

2200

459

0.41

384

550

0.62

575

625

0.83

778

690

1.07

994

748

1.31

1221

2250

465

0.43

402

555

0.64

596

629

0.86

802

694

1.10

1021

753

1.34

1252

2300

471

0.45

421

560

0.66

618

634

0.89

828

699

1.13

1050

757

1.38

1283

2400

483

0.49

461

571

0.71

665

644

0.94

881

708

1.19

1109

766

1.45

1348

2500

495

0.54

503

581

0.77

715

654

1.01

937

717

1.26

1171

775

1.52

1416

2550

501

0.56

526

587

0.79

740

659

1.04

967

722

1.29

1204

779

1.56

1452

2600

507

0.59

549

592

0.82

767

664

1.07

996

727

1.33

1237

784

1.60

1488

2700

519

0.64

597

603

0.88

823

674

1.14

1059

737

1.40

1306

793

1.68

1563

2800

532

0.70

649

614

0.95

882

684

1.21

1125

746

1.48

1378

803

1.76

1641

2900

544

0.75

703

625

1.01

944

695

1.28

1194

756

1.56

1453

812

1.85

1723

3000

557

0.82

761

637

1.08

1009

705

1.36

1266

766

1.64

1533

822

1.94

1808

3100

570

0.88

823

648

1.16

1079

716

1.44

1342

776

1.73

1615

831

2.03

1897

3200

583

0.95

888

660

1.23

1151

727

1.53

1422

787

1.82

1702

841

2.13

1991

3300

596

1.03

957

672

1.32

1228

738

1.61

1506

797

1.92

1792

851

2.24

2088

3400

609

1.10

1030

684

1.40

1308

749

1.71

1593

808

2.02

1887

861

2.35

2188

3500

622

1.19

1106

696

1.49

1392

760

1.81

1685

818

2.13

1985

3600

635

1.27

1187

708

1.59

1481

771

1.91

1781

829

2.24

2088

3700

649

1.36

1272

720

1.69

1573

783

2.02

1881

840

2.35

2195

3750

655

1.41

1316

726

1.74

1621

789

2.07

1932

3800

662

1.46

1361

732

1.79

1670

794

2.13

1985

3900

675

1.56

1454

745

1.90

1771

806

2.25

2093

4000

689

1.66

1553

757

2.01

1877

818

2.37

2207

4100

703

1.77

1655

770

2.13

1988

4200

716

1.89

1762

782

2.25

2103

4250

723

1.95

1818

789

2.32

2162

 

 

 

 

 

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

1.2

 

 

1.4

 

 

1.6

 

 

1.8

 

 

2.0

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

2200

802

1.57

1461

852

1.83

1711

899

2.11

1971

943

2.40

2241

2250

806

1.60

1494

856

1.87

1747

903

2.15

2009

2300

811

1.64

1528

860

1.91

1784

907

2.20

2048

2400

819

1.71

1599

868

1.99

1859

915

2.28

2129

2500

828

1.79

1672

877

2.08

1938

923

2.37

2214

2550

832

1.83

1710

881

2.12

1979

2600

836

1.88

1749

885

2.17

2021

2700

845

1.96

1830

894

2.26

2107

2800

854

2.05

1914

903

2.36

2197

2900

864

2.15

2002

3000

873

2.24

2093

3100

882

2.35

2189

3200

3300

3400

3500

3600

3700

3750

3800

3900

4000

4100

4200

4250

LEGEND

Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor

*Motor drive range: 685 to 935 rpm. All other rpms require field- supplied drive.

NOTES:

1.Boldface indicates field-supplied drive is required.

2.Maximum continuous bhp is 2.40.

3.See page 33 for general fan performance notes.

47