Table 18 — Fan Performance 558F150,151 — Vertical Discharge Units; Standard Motor (Belt Drive)*

AIRFLOW

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

0.2

 

 

0.4

 

 

0.6

 

 

0.8

 

 

1.0

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

3800

668

1.20

1116

726

1.39

1299

779

1.59

1481

828

1.78

1662

874

1.98

1844

3900

683

1.28

1197

739

1.48

1385

792

1.69

1572

840

1.88

1758

886

2.08

1943

4000

697

1.37

1281

753

1.58

1474

804

1.79

1666

852

1.99

1857

897

2.20

2048

4100

712

1.47

1370

766

1.68

1567

817

1.89

1764

864

2.10

1960

909

2.31

2155

4200

726

1.57

1462

780

1.79

1665

830

2.00

1866

876

2.22

2067

920

2.43

2268

4300

741

1.67

1559

794

1.89

1767

843

2.12

1973

889

2.34

2179

932

2.56

2384

4400

755

1.78

1660

807

2.01

1873

856

2.23

2084

901

2.46

2295

944

2.69

2505

4500

770

1.89

1766

821

2.13

1984

869

2.36

2200

914

2.59

2415

956

2.82

2630

4600

785

2.01

1876

835

2.25

2099

882

2.49

2320

926

2.72

2541

968

2.96

2760

4700

800

2.14

1991

849

2.38

2219

895

2.62

2445

939

2.86

2670

980

3.10

2895

4800

815

2.26

2111

863

2.51

2344

909

2.76

2575

952

3.01

2805

993

3.25

3034

4900

829

2.40

2235

877

2.65

2473

922

2.91

2709

965

3.16

2944

1005

3.41

3178

5000

844

2.54

2365

891

2.80

2608

936

3.06

2849

978

3.31

3089

1018

3.57

3328

5100

859

2.68

2499

906

2.95

2747

949

3.21

2994

991

3.47

3238

5200

874

2.83

2640

920

3.10

2892

963

3.37

3143

1004

3.64

3393

5300

889

2.99

2784

934

3.26

3042

977

3.54

3298

5400

904

3.15

2936

949

3.43

3198

5500

920

3.32

3092

963

3.60

3359

5600

935

3.49

3253

5700

950

3.67

3421

5800

5900

6000

6100

6200

6300

 

 

 

 

 

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

1.2

 

 

1.4

 

 

1.6

 

 

1.8

 

 

2.0

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

3800

918

2.17

2025

959

2.37

2207

999

2.56

2389

1036

2.76

2571

1073

2.95

2755

3900

929

2.28

2130

970

2.48

2316

1009

2.68

2502

1046

2.88

2690

1082

3.09

2877

4000

940

2.40

2238

980

2.61

2429

1019

2.81

2620

1056

3.02

2812

1092

3.22

3004

4100

951

2.52

2351

991

2.73

2547

1029

2.94

2743

1066

3.15

2939

1102

3.36

3136

4200

962

2.65

2468

1002

2.86

2668

1040

3.08

2869

1076

3.29

3070

1112

3.51

3271

4300

973

2.78

2589

1013

3.00

2794

1050

3.22

2999

1087

3.44

3205

1122

3.66

3411

4400

985

2.91

2715

1024

3.14

2924

1061

3.36

3134

1097

3.59

3345

4500

996

3.05

2845

1035

3.28

3059

1072

3.51

3274

4600

1008

3.20

2979

1046

3.43

3199

1083

3.67

3418

4700

1020

3.34

3119

1058

3.58

3343

4800

1032

3.50

3263

4900

1044

3.66

3413

5000

5100

5200

5300

5400

5500

5600

5700

5800

5900

6000

6100

6200

6300

LEGEND

Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor

*Motor drive range: 860 to 1080 rpm. All other rpms require field- supplied drive.

NOTES:

1.Boldface indicates field-supplied drive is required.

2.Maximum continuous bhp is 3.70.

3.See page 33 for general fan performance notes.