Table 31 — EconoMi$er IV Input/Output Logic
| INPUTS |
|
|
|
|
| OUTPUTS |
| |
Demand Control | Enthalpy* |
|
|
| Compressor | N Terminal† | |||
|
| Y1 | Y2 | Stage | Stage | Occupied | Unoccupied | ||
Ventilation (DCV) | Outdoor | Return | |||||||
|
| 1 | 2 | Damper | |||||
|
|
|
|
| |||||
Below set | High | Low | On | On | On | On | Minimum position | Closed | |
(DCV LED Off) | (Free Cooling LED Off) |
|
|
|
|
|
|
| |
| On | Off | On | Off |
|
| |||
|
|
|
|
| |||||
|
|
| Off | Off | Off | Off |
|
| |
| Low | High | On | On | On | Off | Modulating** (between min. | Modulating** (between | |
| (Free Cooling LED On) |
|
|
|
|
| position and | closed and | |
|
| On | Off | Off | Off | ||||
|
|
|
|
| |||||
|
|
| Off | Off | Off | Off | Minimum position | Closed | |
Above set | High | Low | On | On | On | On | Modulating†† (between min. | Modulating†† (between | |
(DCV LED On) | (Free Cooling LED Off) |
|
|
|
|
| position and DCV maximum) | closed and DCV | |
| On | Off | On | Off | |||||
|
|
|
| maximum) | |||||
|
|
| Off | Off | Off | Off |
| ||
|
|
|
|
| |||||
| Low | High | On | On | On | Off | Modulating*** | Modulating††† | |
| (Free Cooling LED On) |
|
|
|
|
|
|
| |
|
| On | Off | Off | Off |
|
| ||
|
|
|
|
| |||||
|
|
| Off | Off | Off | Off |
|
|
*For single enthalpy control, the module compares outdoor enthalpy to the ABCD set point.
†Power at N terminal determines Occupied/Unoccupied setting: 24 vac (Occupied), no power (Unoccupied).
**Modulation is based on the supply air sensor signal. ††Modulation is based on the DCV signal.
***Modulation is based on the greater of DCV and supply air sensor signals, between minimum position and either maximum position (DCV) or fully open (supply air signal).
†††Modulation is based on the greater of DCV and supply air sensor signals, between closed and either maximum position (DCV) or fully open (supply air signal).