Bryant 558F EconoMi$er IV Wiring, Outdoor-AirDamper Leakage, Return-AirPressure Drop

Models: 558F

1 70
Download 70 pages 22.19 Kb
Page 25
Image 25
Fig. 23 — EconoMi$er IV Wiring

FOR OCCUPANCY CONTROL REPLACE JUMPER WITH FIELD-SUPPLIED TIME CLOCK

LEGEND

Potentiometer Defaults Settings:

DCV — Demand Controlled Ventilation

Power Exhaust

Middle

Minimum Pos.

Fully Closed

IAQ — Indoor Air Quality

DCV Max.

Middle

LA — Low Ambient Lockout Device

DCV Set

Middle

OAT — Outdoor-Air Temperature

Enthalpy

C Setting

POT — Potentiometer

 

 

RAT — Return-Air Temperature

NOTES:

1.620 ohm, 1 watt 5% resistor should be removed only when using differential enthalpy or dry bulb.

2.If a separate field-supplied 24 v transformer is used for the IAQ sensor power supply, it cannot have the secondary of the transformer grounded.

3.For field-installed remote minimum position POT, remove black wire jumper between P and P1 and set control minimum position POT to the minimum position.

Fig. 23 — EconoMi$er IV Wiring

(cfm)

2500

 

 

 

 

 

 

 

 

 

 

 

MINUTE

2000

 

 

 

 

 

 

 

 

 

 

 

PER

1500

 

 

 

 

 

 

 

 

 

 

 

FEET

 

 

 

 

 

 

 

 

 

 

 

1000

 

 

 

 

 

 

 

 

 

 

 

CUBICIN

 

 

 

 

 

 

 

 

 

 

 

500

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FLOW

0

 

 

 

 

 

 

 

 

 

 

 

 

 

0.05

 

 

0.15

 

 

0.25

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STATIC PRESSURE (in. wg)

 

 

 

 

 

 

Fig. 24 — Barometric Flow Capacity

 

 

(cfm)

30

 

 

 

 

 

 

 

 

 

 

 

 

 

MINUTE

 

 

 

 

 

 

 

 

 

 

 

 

 

25

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PER

20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15

 

 

 

 

 

 

 

 

 

 

 

 

 

FEET

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CUBICIN

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

 

 

 

 

 

 

 

 

 

 

 

 

 

FLOW

0.13

0.20

0.22

0.25

0.30

0.35

0.40

0.45

0.50

 

 

 

 

 

 

 

STATIC PRESSURE (in. wg)

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 25 — Outdoor-Air Damper Leakage

(cfm)

6000

 

 

 

 

 

 

 

 

MINUTE

5000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PER

4000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3000

 

 

 

 

 

 

 

 

FEET

 

 

 

 

 

 

 

 

2000

 

 

 

 

 

 

 

 

CUBIC

 

 

 

 

 

 

 

 

1000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IN

 

 

 

 

 

 

 

 

 

FLOW

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.05

0.10

0.15

0.20

0.25

0.30

0.35

STATIC PRESSURE (in. wg)

Fig. 26 — Return-Air Pressure Drop

D. EconoMi$er IV Standard Sensors

Outdoor Air Temperature (OAT) Sensor

The outdoor air temperature sensor (HH57AC074) is a 10 to 20 mA device used to measure the outdoor-air temperature. The outdoor-air temperature is used to determine when the EconoMi$er IV can be used for free cooling. The sensor is factory-installed on the EconoMi$er IV in the outdoor airstream. See Fig. 17. The operating range of temperature measurement is 40 to 100 F.

Supply Air Temperature (SAT) Sensor

The supply air temperature sensor is a 3 K thermistor located at the inlet of the indoor fan. See Fig. 27. This sensor is factory installed. The operating range of temperature mea- surement is 0° to 158 F. See Table 3 for sensor temperature/ resistance values.

25