Table 30 — Cooling Service Analysis

PROBLEM

CAUSE

REMEDY

Compressor and

Power failure.

Call power company.

Condenser Fans

 

 

Fuse blown or circuit breaker tripped.

Replace fuse or reset circuit breaker.

Will Not start.

Defective thermostat, contactor, transformer, or

Replace component.

 

 

control relay.

 

 

Insufficient line voltage.

Determine cause and correct.

 

Incorrect or faulty wiring.

Check wiring diagram and rewire correctly.

 

Thermostat setting too high.

Lower thermostat setting below room temperature.

Compressor Will Not Start

Faulty wiring or loose connections in compressor

Check wiring and repair or replace.

But Condenser Fans Run.

circuit.

 

 

Compressor motor burned out, seized, or internal

Determine cause. Replace compressor.

 

overload open.

 

 

Defective run/start capacitor, overload, or start

Determine cause and replace.

 

relay.

 

 

One leg of 3-phase power dead.

Replace fuse or reset circuit breaker.

 

 

Determine cause.

Compressor Cycles

Refrigerant overcharge or undercharge.

Recover refrigerant, evacuate system, and recharge

(Other Than Normally

 

to nameplate.

Satisfying Thermostat).

 

 

Defective compressor.

Replace and determine cause.

 

 

Insufficient line voltage.

Determine cause and correct.

 

Blocked condenser.

Determine cause and correct.

 

Defective run/start capacitor, overload, or start

Determine cause and replace.

 

relay.

 

 

Defective thermostat.

Replace thermostat.

 

Faulty condenser-fan motor or capacitor.

Replace.

 

Restriction in refrigerant system.

Locate restriction and remove.

Compressor Operates

Dirty air filter.

Replace filter.

Continuously.

 

 

Unit undersized for load.

Decrease load or increase unit size.

 

 

Thermostat set too low.

Reset thermostat.

 

Low refrigerant charge.

Locate leak, repair, and recharge.

 

Leaking valves in compressor.

Replace compressor.

 

Air in system.

Recover refrigerant, evacuate system, and recharge.

 

Condenser coil dirty or restricted.

Clean coil or remove restriction.

Compressor Makes Exces-

Compressor rotating in wrong direction

Reverse the 3-phase power leads as described in

sive Noise (558F103,121,

 

Start-Up section, page 54.

150,151 Scroll Only).

 

 

Excessive Head Pressure.

Dirty air filter.

Replace filter.

 

Dirty condenser coil.

Clean coil.

 

Refrigerant overcharged.

Remove excess refrigerant.

 

Air in system.

Recover refrigerant, evacuate system, and recharge.

 

Condenser air restricted or air short-cycling.

Determine cause and correct.

 

Outdoor fan contactor not energized.

Verify outdoor fan coil receiving 24 vac and high voltage

 

 

contacts close.

Head Pressure Too Low.

Low refrigerant charge.

Check for leaks, repair, and recharge.

 

Compressor valves leaking.

Replace compressor.

 

Restriction in liquid tube.

Remove restriction.

Excessive Suction

High heat load.

Check for source and eliminate.

Pressure.

 

 

Compressor valves leaking.

Replace compressor.

 

 

Refrigerant overcharged.

Recover excess refrigerant.

Suction Pressure Too Low.

Dirty air filter.

Replace filter.

 

Low refrigerant charge.

Check for leaks, repair, and recharge.

 

Metering device or low side restricted.

Remove source of restriction.

 

Insufficient evaporator airflow.

Increase air quantity. Check filter and replace if

 

 

necessary.

 

Temperature too low in conditioned area.

Reset thermostat.

 

Field-installed filter drier restricted.

Replace.

Compressor No. 2

Unit in economizer mode.

Proper operation; no remedy necessary.

Will Not Run.

 

 

64

Page 64
Image 64
Bryant 558F installation instructions Cooling Service Analysis

558F specifications

The Bryant 558F is a highly efficient and versatile gas furnace designed to provide reliable heating for residential spaces. Known for its exceptional performance and advanced technology, the 558F caters to homeowners looking for comfort, efficiency, and sustainability in their heating solutions.

One of the primary features of the Bryant 558F is its two-stage heating capability. This system allows the furnace to operate at different levels of output, optimizing energy consumption based on the heating demands of the home. By operating at a lower stage most of the time, the 558F can maintain consistent indoor temperatures while using less energy, leading to reduced utility bills.

The furnace is also equipped with aVariable Speed ECM blower motor. This feature provides enhanced air distribution and comfort by allowing for more precise control over airflow. The variable speed operation ensures that the furnace can adjust to the heating needs of the space without the constant on-off cycling, promoting quieter operation and better efficiency.

In terms of efficiency ratings, the Bryant 558F boasts an impressive Annual Fuel Utilization Efficiency (AFUE) rating of up to 96%. This high rating indicates that the furnace converts a significant portion of its fuel into usable heat, making it an environmentally friendly choice. With lower greenhouse gas emissions, homeowners not only benefit from cost savings but also contribute to reducing their carbon footprint.

Additionally, the furnace incorporates advanced combustion technology, including a durable heat exchanger designed for longevity and efficiency. This component is vital for maximizing heat transfer while minimizing heat loss, contributing to the overall performance of the unit.

The Bryant 558F is compatible with the manufacturer's Infinity System control, providing homeowners with a user-friendly interface to manage their heating system effectively. This compatibility allows for the integration of smart home technology, enabling remote access and programmable settings for added convenience.

Installation and maintenance of the Bryant 558F are straightforward, thanks to its compact design and thoughtful layout. Homeowners can find peace of mind knowing that service and upkeep are manageable, prolonging the life of the furnace.

In summary, the Bryant 558F gas furnace combines efficiency, advanced technology, and reliability to provide exceptional indoor comfort. With its two-stage heating, variable speed blower motor, and high AFUE rating, the 558F stands out as an optimal heating solution for modern homes seeking both performance and sustainability.