Bryant 558F installation instructions

Models: 558F

1 70
Download 70 pages 22.19 Kb
Page 48
Image 48

Table 24 — Fan Performance 558F102,103 — Horizontal Discharge Units; High-Static Motor (Belt Drive)*

AIRFLOW

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

0.2

 

 

0.4

 

 

0.6

 

 

0.8

 

 

1.0

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

2200

459

0.41

384

550

0.62

575

625

0.83

778

690

1.07

994

748

1.31

1221

2250

465

0.43

402

555

0.64

596

629

0.86

802

694

1.10

1021

753

1.34

1252

2300

471

0.45

421

560

0.66

618

634

0.89

828

699

1.13

1050

757

1.38

1283

2400

483

0.49

461

571

0.71

665

644

0.94

881

708

1.19

1109

766

1.45

1348

2500

495

0.54

503

581

0.77

715

654

1.01

937

717

1.26

1171

775

1.52

1416

2550

501

0.56

526

587

0.79

740

659

1.04

967

722

1.29

1204

779

1.56

1452

2600

507

0.59

549

592

0.82

767

664

1.07

996

727

1.33

1237

784

1.60

1488

2700

519

0.64

597

603

0.88

823

674

1.14

1059

737

1.40

1306

793

1.68

1563

2800

532

0.70

649

614

0.95

882

684

1.21

1125

746

1.48

1378

803

1.76

1641

2900

544

0.75

703

625

1.01

944

695

1.28

1194

756

1.56

1453

812

1.85

1723

3000

557

0.82

761

637

1.08

1009

705

1.36

1266

766

1.64

1533

822

1.94

1808

3100

570

0.88

823

648

1.16

1079

716

1.44

1342

776

1.73

1615

831

2.03

1897

3200

583

0.95

888

660

1.23

1151

727

1.53

1422

787

1.82

1702

841

2.13

1991

3300

596

1.03

957

672

1.32

1228

738

1.61

1506

797

1.92

1792

851

2.24

2088

3400

609

1.10

1030

684

1.40

1308

749

1.71

1593

808

2.02

1887

861

2.35

2188

3500

622

1.19

1106

696

1.49

1392

760

1.81

1685

818

2.13

1985

872

2.46

2294

3600

635

1.27

1187

708

1.59

1481

771

1.91

1781

829

2.24

2088

882

2.58

2403

3700

649

1.36

1272

720

1.69

1573

783

2.02

1881

840

2.35

2195

892

2.70

2517

3750

655

1.41

1316

726

1.74

1621

789

2.07

1932

845

2.41

2250

897

2.76

2575

3800

662

1.46

1361

732

1.79

1670

794

2.13

1985

851

2.47

2307

903

2.83

2635

3900

675

1.56

1454

745

1.90

1771

806

2.25

2093

862

2.60

2422

913

2.96

2758

4000

689

1.66

1553

757

2.01

1877

818

2.37

2207

873

2.73

2543

924

3.09

2886

4100

703

1.77

1655

770

2.13

1988

830

2.49

2325

884

2.86

2668

935

3.24

3018

4200

716

1.89

1762

782

2.25

2103

842

2.62

2447

896

3.00

2798

946

3.38

3155

4250

723

1.95

1818

789

2.32

2162

848

2.69

2511

901

3.07

2865

951

3.46

3226

 

 

 

 

 

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

1.2

 

 

1.4

 

 

1.6

 

 

1.8

 

 

2.0

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

2200

802

1.57

1461

852

1.83

1711

899

2.11

1971

943

2.40

2241

985

2.70

2521

2250

806

1.60

1494

856

1.87

1747

903

2.15

2009

947

2.45

2282

988

2.75

2564

2300

811

1.64

1528

860

1.91

1784

907

2.20

2048

950

2.49

2323

992

2.80

2607

2400

819

1.71

1599

868

1.99

1859

915

2.28

2129

958

2.58

2410

1000

2.89

2698

2500

828

1.79

1672

877

2.08

1938

923

2.37

2214

966

2.68

2499

1008

3.00

2793

2550

832

1.83

1710

881

2.12

1979

927

2.42

2258

971

2.73

2545

1012

3.05

2842

2600

836

1.88

1749

885

2.17

2021

931

2.47

2302

975

2.78

2592

1016

3.10

2891

2700

845

1.96

1830

894

2.26

2107

940

2.57

2394

983

2.88

2689

1024

3.21

2993

2800

854

2.05

1914

903

2.36

2197

948

2.67

2488

991

2.99

2790

1032

3.32

3099

2900

864

2.15

2002

912

2.46

2290

957

2.77

2587

1000

3.10

2894

1041

3.44

3209

3000

873

2.24

2093

921

2.56

2388

966

2.89

2691

1008

3.22

3003

1049

3.56

3323

3100

882

2.35

2189

930

2.67

2489

975

3.00

2798

1017

3.34

3115

1057

3.69

3441

3200

892

2.45

2288

939

2.78

2595

984

3.12

2909

1026

3.47

3233

3300

901

2.56

2391

948

2.90

2704

993

3.24

3024

1035

3.60

3353

3400

911

2.68

2499

958

3.02

2817

1002

3.37

3144

3500

921

2.80

2610

967

3.15

2935

1011

3.50

3268

3600

931

2.92

2726

977

3.28

3057

1021

3.64

3396

3700

941

3.05

2847

987

3.41

3184

3750

946

3.12

2908

992

3.48

3249

3800

951

3.19

2971

997

3.56

3316

3900

961

3.33

3101

1007

3.70

3451

4000

972

3.47

3235

4100

982

3.62

3375

4200

4250

LEGEND

Bhp — Brake Horsepower Input to Fan Watts — Input Watts to Motor

*Motor drive range: 860 to 1080 rpm. All other rpms require field- supplied drive.

NOTES:

1.Boldface indicates field-supplied drive is required.

2.Maximum continuous bhp is 3.70.

3.See page 33 for general fan performance notes.

48

Page 48
Image 48
Bryant 558F installation instructions