Table 11 – PHYSICAL DATA

Table 11 – PHYSICAL DATA

(COOLING)

 

 

10 - 15 TONS

 

 

 

 

 

 

 

 

580J*12A

580J*12D

580J*14D

580J*16D

Refrigeration System

 

 

 

 

 

 

# Circuits / # Comp. / Type

RTPF models R

---410a charge A/B (lbs ---

oz)

Alternate (MCHX) R

---410a charge A/B (lbs ---

oz)

Alternate (Perfect Humidity) R

---410a charge A/B (lbs ---

oz)

 

 

Metering device

High ---

press. Trip / Reset (psig)

Low---

press. Trip / Reset (psig)

Loss of charge Trip / Reset (psig)

Evap. Coil

1 / 1 / Scroll

20 --- 0

---

---

Accutrol 630 / 505 54 / 117

---

2 / 2 / Scroll

10 --- 5 / 10 --- 3

6 --- 0 / 6 --- 0

16 --- 10 / 16 --- 0

Accutrol

630 / 505

54 / 117

---

2 / 2 / Scroll

11 --- 0 / 11 --- 6

7 --- 6 / 8 --- 0

17 --- 10 / 18 --- 3

Accutrol

630 / 505

54 / 117

---

2 / 2 / Scroll

15---14/16---12

---

---

Accutrol 630 / 505 54 / 117

---

580J

Material

Cu / Al

Cu / Al

Cu / Al

Cu / Al

Coil type

3/8” RTPF

3/8” RTPF

3/8” RTPF

3/8” RTPF

Rows / FPI

4 / 15

4 / 15

4 / 15

3 / 15

total face area (ft2)

11.1

11.1

11.1

17.5

Condensate drain conn. size

3/4”

3/4”

3/4”

3/4”

 

 

 

 

 

Perfect Humidity Coil

 

 

 

 

Material

---

Cu / Al

Cu / Al

---

Coil type

---

3/8” RTPF

3/8” RTPF

---

Rows / FPI

---

2 / 17

2 / 17

---

total face area (ft2)

---

8.4

8.4

---

Evap. fan and motor

 

 

 

 

Standard Static

3 phase

 

 

Medium Static

3 phase

 

 

High Static

3 phase

 

 

High Static

--High Efficiency 3 phase*

Cond. Coil

Motor Qty / Drive type Max BHP RPM range

motor frame size Fan Qty / Type Fan Diameter (in)

Motor Qty / Drive type Max BHP RPM range

motor frame size Fan Qty / Type Fan Diameter (in)

Motor Qty / Drive type Max BHP RPM range

motor frame size Fan Qty / Type Fan Diameter (in)

Motor Qty / Drive type Max BHP RPM range

motor frame size Fan Qty / Type Fan Diameter (in)

1 / Belt

2.4

591---838 56

1/ Centrifugal 15 x 15

1 / Belt

3.7

838---1084 56

1/ Centrifugal 15 x 15

1 / Belt

4.7

1022---1240

14

1 / Centrifugal

15 x 15

1 / Belt

2.4

591---838 56

1/ Centrifugal 15 x 15

1 / Belt

3.7

838---1084 56

1/ Centrifugal 15 x 15

1 / Belt

4.7

1022---1240

14

1 / Centrifugal

15 x 15

15 x 15

1 / Belt

2.9

652---843 56

1/ Centrifugal 15 x 15

1 / Belt

3.7

838---1084 56

1/ Centrifugal 15 x 15

1 / Belt

4.7

1022---1240

14

1 / Centrifugal

15 x 15

1 / Belt

2.9

507---676 56

1/ Centrifugal 18 x 18

1 / Belt

3.7

627---851 56

1 / Centrifugal

18 x 18

1 / Belt

6.1

776---955

S184T

1/ Centrifugal 18 x 18

1 / Belt

6.1

776---955

S184T

1 / Centrifugal

18 x 18

Material

Cu / Al

Cu / Al

Cu / Al

Cu / Al

Coil type

3/8” RTPF

3/8” RTPF

3/8” RTPF

3/8” RTPF

Rows / FPI

2 / 17

2 / 17

3 / 17

2/17

total face area (ft2)

25.1

25.1

25.1

2 @ 23.1

 

 

 

 

 

Alternate (MCHX) Cond. Coil

 

 

 

 

Material

---

Al / Al

Al / Al

---

Coil type

---

Novation

Novation

---

Rows / FPI

---

1 / 20

2 / 20

---

total face area (ft2)

---

25.1

25.1

---

 

 

 

 

 

Cond. fan / motor

 

 

 

 

Qty / Motor drive type

2 / direct

2 / direct

1 / direct

3 / direct

Motor HP / RPM

1/4 / 1100

1/4 / 1100

1 / 1175

1/4 / 1100

Fan diameter (in)

22

22

30

22

 

 

 

 

 

Filters

 

 

 

 

RA Filter # / Size (in)

4 / 20 x 20 x 2

4 / 20 x 20 x 2

4 / 20 x 20 x 2

16 / 18 x 24 x 2

 

 

 

 

V2 / 24 x 27 x 1

OA inlet screen # / Size (in)

1 / 20 x 24 x 1

1 / 20 x 24 x 1

1 / 20 x 24 x 1

H1 / 30 x 39 x 1

NOTE: Perfect Humidity is not available with Novation condenser coil models. Only Round Tube/Plate Fin (RTPF) up to 14 size.

*Section 313 of the Energy Independence and Security Act of 2007 (EISA 2007) mandates that the efficiency of general purpose motors we use in our Light Commercial Rooftops rated at 5.0HP and larger be increased on or after December 19, 2010. We will offer both high and standard efficient motors until inventory is depleted and then shift over solely to the high efficient motors only.

16