Bryant manual CURBS & WEIGHTS DIMENSIONS - 580J 04-07cont, Dimensions 580J, Service Clearance

Models: 580J

1 94
Download 94 pages 40.55 Kb
Page 19
Image 19
CURBS & WEIGHTS DIMENSIONS - 580J 04-07 (cont.)

CURBS & WEIGHTS DIMENSIONS - 580J 04-07 (cont.)

580J

C

B

C101226

Fig. 2 - Dimensions 580J 04-07

D

A

C08337

 

 

Fig. 3 - Service Clearance

 

 

 

LOC

DIMENSION

CONDITION

 

48--- in (1219 mm)

Unit disconnect is mounted on panel

A

18--- in (457 mm)

No disconnect, convenience outlet option

18--- in (457 mm)

Recommended service clearance

 

 

12--- in (305 mm)

Minimum clearance

 

 

 

 

42--- in (1067 mm)

Surface behind servicer is grounded (e.g., metal, masonry wall)

B

36--- in (914 mm)

Surface behind servicer is electrically non--- conductive (e.g., wood, fiberglass)

 

Special

Check for sources of flue products within 10--- ft of unit fresh air intake hood

 

 

 

C

36--- in (914 mm)

Side condensate drain is used

18--- in (457 mm)

Minimum clearance

 

 

 

 

 

48--- in (1219 mm)

No flue discharge accessory installed, surface is combustible material

D

42--- in (1067 mm)

Surface behind servicer is grounded (e.g., metal, masonry wall, another unit)

36--- in (914 mm)

Surface behind servicer is electrically non--- conductive (e.g., wood, fiberglass)

 

 

Special

Check for adjacent units or building fresh air intakes within 10--- ft of this unit’s flue outlet

 

 

 

19

Page 19
Image 19
Bryant manual CURBS & WEIGHTS DIMENSIONS - 580J 04-07cont, Dimensions 580J, Service Clearance