Table 20 – COOLING CAPACITIES
tldb = tedb

580J

Table 20 – COOLING CAPACITIES

1-STAGE COOLING

 

 

 

6 TONS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

580J07 (6 TONS) --- UNIT WITH PERFECT HUMIDITY SYSTEM IN SUBCOOLING MODE

 

 

 

 

 

 

Air Entering Evaporator --- CFM

 

 

 

 

Temp (F) Air Ent

 

 

80 dry bulb

 

 

80 dry bulb

 

 

80 dry bulb

 

 

 

72 wet bulb

 

 

67 wet bulb

 

 

62 wet bulb

 

Condenser (Edb)

 

 

 

 

 

 

 

 

 

 

2100

2400

2700

2100

2400

2700

2100

2400

2700

 

TC

 

86.7

89.9

92.8

79.3

82.3

84.9

71.9

74.6

77.0

75

SHC

 

40.1

41.8

43.3

46.9

48.5

49.9

53.7

55.2

56.5

 

kW

 

4.3

4.3

4.3

4.2

4.2

4.2

4.2

4.2

4.2

 

TC

 

79.5

82.6

85.4

72.5

75.3

77.9

65.4

68.0

70.3

85

SHC

 

32.1

34.0

35.7

40.7

42.5

44.1

49.4

51.0

52.5

 

kW

 

5.0

5.0

5.0

5.0

5.0

5.0

4.9

4.9

4.9

 

TC

 

72.4

75.3

78.1

65.6

68.3

70.8

58.8

61.3

63.6

95

 

 

 

 

 

 

 

 

 

 

 

SHC

 

24.1

26.3

28.1

34.6

36.6

38.3

45.1

46.9

48.5

 

kW

 

5.8

5.8

5.8

5.7

5.7

5.7

5.6

5.6

5.6

 

TC

 

65.2

68.1

70.7

58.7

61.4

63.8

52.3

54.7

56.8

105

 

 

 

 

 

 

 

 

 

 

 

SHC

 

16.2

18.5

20.5

28.5

30.6

32.6

40.7

42.8

44.6

 

kW

 

6.5

6.5

6.5

6.4

6.4

6.4

6.3

6.3

6.3

 

TC

 

58.0

60.8

63.3

51.9

54.4

56.7

45.7

48.0

50.1

115

SHC

 

8.2

10.7

13.0

22.3

24.7

26.8

36.4

38.6

40.6

 

kW

 

7.2

7.2

7.2

7.1

7.1

7.1

7.0

7.0

7.0

 

 

 

 

 

 

580J07 (6 TONS) --- UNIT WITH PERFECT HUMIDITY SYSTEM IN HOT GAS REHEAT MODE

 

 

 

 

 

 

Air Entering Evaporator --- CFM

 

 

 

 

Temp (F) Air Ent

 

 

75 dry bulb

 

 

75 dry bulb

 

 

75 dry bulb

 

 

62.5 wet bulb (50% relative)

64 wet bulb (55% relative)

65.3 wet bulb (60% relative)

Condenser (Edb)

 

 

 

 

2100

2400

2700

2100

2400

2700

1750

2000

2700

 

TC

 

16.7

19.8

22.5

18.8

21.9

24.7

16.2

19.4

26.7

80

SHC

 

0.6

0.6

0.6

--- 0.4

--- 0.4

--- 0.4

--- 1.3

--- 1.3

--- 1.3

 

kW

 

4.0

4.0

4.0

4.0

4.0

4.0

4.0

4.0

4.0

 

TC

 

17.7

20.6

23.1

19.6

22.6

25.3

17.3

20.3

27.1

75

SHC

 

0.6

0.6

0.6

--- 0.3

--- 0.3

--- 0.3

--- 1.2

--- 1.2

--- 1.2

 

kW

 

4.0

4.0

4.0

4.0

4.0

4.0

4.0

4.0

4.0

 

TC

 

18.6

21.3

23.7

20.5

23.3

25.8

18.3

21.1

27.6

70

 

 

 

 

 

 

 

 

 

 

 

SHC

 

0.7

0.7

0.7

--- 0.2

--- 0.2

--- 0.2

--- 1.0

--- 1.0

--- 1.0

 

kW

 

4.0

4.0

4.0

4.1

4.1

4.1

4.1

4.1

4.1

 

TC

 

20.5

22.9

25.0

22.2

24.7

26.8

20.4

22.8

28.5

60

 

 

 

 

 

 

 

 

 

 

 

SHC

 

0.7

0.7

0.7

--- 0.0

--- 0.0

--- 0.0

--- 0.7

--- 0.7

--- 0.7

 

kW

 

4.1

4.1

4.1

4.1

4.1

4.1

4.1

4.1

4.1

 

TC

 

22.4

24.4

26.2

24.0

26.0

27.9

22.4

24.5

29.3

50

SHC

 

0.8

0.8

0.8

0.1

0.1

0.1

--- 0.4

--- 0.4

--- 0.4

 

kW

 

4.1

4.1

4.1

4.1

4.1

4.1

4.2

4.2

4.2

 

TC

 

24.3

25.9

27.4

25.7

27.4

28.9

24.5

26.3

30.2

40

SHC

 

0.8

0.8

0.8

0.3

0.3

0.3

--- 0.1

--- 0.1

--- 0.1

 

kW

 

4.1

4.1

4.1

4.2

4.2

4.2

4.2

4.2

4.2

LEGEND

 

Edb

---

Entering Dry--- Bulb

Ewb

---

Entering Wet--- Bulb

kW

---

Compressor Motor Power Input

Idb

---

Leaving Dry--- Bulb

Iwb

---

Leaving Wet--- Bulb

SHC ---

Sensible Heat Capacity (1000 Btuh) Gross

TC

---

Total Capacity (1000 Btuh) Gross

NOTES:

1.Direct interpolation is permissible. Do not extrapolate.

2.The following formulas may be used:

sensible capacity (Btuh)

1.10 x cfm

tlwb = Wet--- bulb temperature corresponding to enthalpy of air leaving evaporator coil (hlwb)

total capacity (Btuh)

hlwb = hewb 4.5 x cfm

Where: hewb = Enthalpy of air entering evaporator coil

40