Table 3 – HEATING RATING TABLE - NATURAL GAS & PROPANE
|
|
|
| AL/SS HEAT EXCHANGER |
| TEMP RISE | THERMAL | AFUE | ||||
Units | Gas Heat |
|
|
|
|
| EFFICIENCY | |||||
INPUT / OUTPUT | INPUT / OUTPUT | (DEG F) | (%) | |||||||||
|
|
| (%) | |||||||||
|
|
| STAGE 1 (MBH) | STAGE 2 (MBH) |
|
|
| |||||
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
| |
|
| LOW |
| 72 | / | 59 | 25 | 82% | 81% | |||
| 04 | MED |
| 115 / 93 | 55 | 80% | 80% | |||||
Phase |
| HIGH |
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
| ||
|
| LOW |
| 72 | / | 59 | 25 | 82% | 81% | |||
Single | 05 | MED |
| 115 / 93 | 35 | 81% | 80% | |||||
| HIGH |
| 150 | / | 120 | 50 | 80% | 80% | ||||
|
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
|
| |
|
| LOW |
| 72 | / | 59 | 20 | 82% | 81% | |||
| 06 | MED |
| 115 / 93 | 30 | 81% | 80% | |||||
|
| HIGH |
| 150 | / | 120 | 40 | 80% | 80% | |||
|
|
|
|
|
|
|
|
|
|
|
| |
|
| LOW |
| 72 | / | 59 | 25 | 82% | N/A | |||
| 04 | MED | 82 | / 66 | 115 / 93 | 55 | 80% | N/A | ||||
|
| HIGH |
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
| |
|
| LOW |
| 72 | / | 59 | 25 | 82% | N/A | |||
| 05 | MED |
| 115 / 93 | 35 | 81% | N/A | |||||
|
| HIGH | 120 / 96 | 150 | / | 120 | 50 | 80% | N/A | |||
|
|
|
|
|
|
|
|
|
|
|
| |
|
| LOW |
| 72 | / | 59 | 20 | 82% | N/A | |||
| 06 | MED |
| 115 / 93 | 30 | 81% | N/A | |||||
|
| HIGH | 120 / 96 | 150 | / | 120 | 40 | 80% | N/A | |||
|
|
|
|
|
|
|
|
|
|
|
| |
|
| LOW |
| 72 | / | 59 | 15 | 82% | N/A | |||
| 07 | MED |
| 115 / 93 | 25 | 81% | N/A | |||||
Phase |
| HIGH | 120 / 96 | 150 | / | 120 | 35 | 80% | N/A | |||
|
|
|
|
|
|
|
|
|
|
| ||
|
| LOW |
| 125 | / | 103 | 20 | 82% | N/A | |||
Three | 08 | MED | 120 / 98 | 180 | / | 148 | 35 | 82% | N/A | |||
| HIGH | 180 | / 147 | 224 | / | 184 | 45 | 82% | N/A | |||
|
| |||||||||||
|
|
|
|
|
|
|
|
|
|
|
| |
|
| LOW |
| 125 | / | 103 | 20 | 82% | N/A | |||
| 09 | MED | 120 / 98 | 180 | / | 148 | 30 | 82% | N/A | |||
|
| HIGH | 180 | / 147 | 224 | / | 184 | 40 | 82% | N/A | ||
|
|
|
|
|
|
|
|
|
|
| ||
|
| LOW | 120 / 98 | 180 | / | 148 | 25 | 82% | N/A | |||
| 12 | MED | 180 | / 147 | 224 | / | 184 | 30 | 82% | N/A | ||
|
| HIGH | 200 | / 160 | 250 | / | 205 | 35 | 80% | N/A | ||
|
|
|
|
|
|
|
|
|
|
| ||
|
| LOW | 120 / 98 | 180 | / | 148 | 20 | 82% | N/A | |||
| 14 | MED | 180 | / 147 | 224 | / | 184 | 25 | 82% | N/A | ||
|
| HIGH | 200 | / 160 | 250 | / | 205 | 25 | 80% | N/A | ||
|
|
|
|
|
|
|
|
|
|
|
| |
|
| LOW | 144 | / 118 | 180 | / | 146 | 15 | 81% | N/A | ||
| 16 | MED | 192 | / 156 | 240 | / | 195 | 20 | 81% | N/A | ||
|
| HIGH | 280 | / 224 | 350 | / | 280 | 35 | 80% | N/A |
NOTES:
Heat ratings are for natural gas heat exchangers operated at or below 2000 ft (610 m). For information on propane or alti- tudes above 2000 ft (610 m), see the Application Data section of this book. Accessory Propane/High Altitude kits are also available.
In the USA the input rating for altitudes above 2000 ft (610m) must be derated by 4% for each 1000 ft (305 m) above sea level. In Canada, the input rating must be derated by 10% for altitudes of 2000 ft (610 m) to 4500 ft (1372 m) above sea level.
580J
9