Bryant 580J manual Winter start kit

Models: 580J

1 94
Download 94 pages 40.55 Kb
Page 93
Image 93
21.Winter start kit

21.Winter start kit

a.Shall contain a bypass device around the low pressure switch.

b.Shall be required when mechanical cooling is required down to 25_F (-4_C).

c.Shall not be required to operate on an economizer when below an outdoor ambient of 40_F (4_C).

22.Time Guard

a.Shall prevent compressor short-cycling by providing a 5-minute delay (±2 minutes) before restarting a com- pressor after shutdown for any reason.

b.One device shall be required per compressor.

580J

93

Page 93
Image 93
Bryant 580J manual Winter start kit