Bryant manual FAN PERFORMANCE cont, 580J**06, Phase, Ton Horizontal Supply, Ton Vertical Supply

Models: 580J

1 94
Download 94 pages 40.55 Kb
Page 61
Image 61
Table 44 – 580J**06

FAN PERFORMANCE (cont.)

Table 44 – 580J**06

 

 

 

3 PHASE

 

5 TON HORIZONTAL SUPPLY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

CFM

0.2

 

 

0.4

0.6

 

0.8

 

 

1.0

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

 

 

 

 

Standard Static Option

 

 

 

 

1500

800

0.39

904

0.49

999

 

0.60

1087

0.72

1169

0.85

1625

849

0.48

947

0.59

1038

 

0.70

1122

0.83

1201

0.96

1750

899

0.59

992

0.70

1078

 

0.82

1159

0.95

1235

1.08

1875

950

0.70

1038

0.82

1120

 

0.95

1198

1.08

1271

1.22

2000

1001

0.84

1085

0.96

1163

 

1.09

1238

1.23

1309

1.38

2125

1053

0.99

1133

1.12

 

 

1.26

1280

1.40

1348

1.55

1208

2250

1106

1.16

1182

1.29

1254

 

1.44

1323

1.59

1389

1.74

2375

1159

1.34

1231

1.49

1300

 

1.64

1367

1.80

1430

1.96

2500

1212

1.55

1281

1.70

1348

 

1.86

1412

2.02

1473

2.19

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

CFM

1.2

 

 

1.4

1.6

 

1.8

 

 

2.0

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

 

 

 

Medium Static Option

 

 

 

High Static Option

1500

1247

0.98

1320

1.13

1390

 

1.28

1457

1.44

1522

1.61

1625

1276

1.10

1348

1.24

1416

 

1.40

1481

1.56

1544

1.73

1750

1308

1.22

1377

1.38

1444

 

1.53

1507

1.70

1569

1.87

1875

1342

1.37

1409

1.52

1473

 

1.69

1536

1.86

1596

2.03

2000

1377

1.53

1442

1.69

1505

 

1.86

1565

2.03

1624

2.21

2125

1414

1.71

 

 

1538

 

2.04

1597

2.22

1654

2.40

1477

1.87

 

2250

1452

1.91

1514

2.08

1573

 

2.25

1630

2.43

1686

2.62

2375

 

 

1551

2.30

1609

 

2.48

1665

2.66

 

 

1492

2.12

 

1719

2.85

2500

1533

2.36

1591

2.54

1647

 

2.73

---

---

---

---

NOTE: For more information, see General Fan Performance Notes. Boldface indicates field supplied drive is required.

1. Recommend using field supplied fan pulley (part no. KR11AZ506), motor pulley (part no. KR11HY191) and belt (part no. KR30AE042).

Table 45 – 580J**06

 

 

 

3 PHASE

 

 

5 TON VERTICAL SUPPLY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

CFM

0.2

 

 

0.4

0.6

 

0.8

 

1.0

 

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

 

 

Standard Static Option

 

 

 

Medium Static Option

 

1500

848

0.42

968

0.55

1069

 

0.68

1158

0.80

1238

0.94

1625

897

0.51

1013

0.65

1111

 

0.79

1198

0.93

1277

1.07

1750

947

0.61

1059

0.76

1155

 

0.91

1240

1.06

1318

1.21

1875

997

0.72

1105

0.89

1199

 

1.05

1283

1.21

1359

1.37

2000

1048

0.85

1153

1.03

1244

 

1.20

1326

1.37

1401

1.54

2125

1100

1.00

 

 

1290

 

1.37

1370

1.55

1444

1.73

1201

1.19

 

2250

1152

1.16

1250

1.36

1336

 

1.55

1415

1.75

1487

1.94

2375

1205

1.34

1299

1.55

1384

 

1.76

1460

1.96

1532

2.17

2500

1258

1.54

1349

1.76

1431

 

1.98

1506

2.20

1576

2.41

 

 

 

 

 

 

 

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

CFM

1.2

 

 

1.4

1.6

 

1.8

 

2.0

 

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

 

 

Medium Static Option

 

 

 

 

High Static Option

 

1500

1312

1.07

1380

1.20

1445

 

1.34

1506

1.48

1564

1.62

1625

1350

1.21

1418

1.35

1482

 

1.50

1542

1.64

1600

1.79

1750

1390

1.36

1457

1.51

1520

 

1.67

1580

1.83

1637

1.98

1875

1430

1.53

 

 

1559

 

1.86

1618

2.02

1675

2.19

1496

1.69

 

2000

1471

1.72

1536

1.89

1598

 

2.06

1657

2.24

1713

2.41

2125

1513

1.92

1577

2.10

1638

 

2.28

1696

2.47

1752

2.65

2250

1555

2.13

1619

2.33

1679

 

2.52

1736

2.72

---

---

2375

1598

2.37

1661

2.57

1720

 

2.78

---

---

---

---

2500

1642

2.63

1704

2.84

---

 

---

---

---

---

---

NOTE: For more information, see General Fan Performance Notes. Boldface indicates field supplied drive is required.

1. Recommend using field supplied fan pulley (part no. KR11AZ506), motor pulley (part no. KR11HY191) and belt (part no. KR30AE042).

580J

61

Page 61
Image 61
Bryant manual FAN PERFORMANCE cont, 580J**06, Phase, Ton Horizontal Supply, Ton Vertical Supply