Table 23 – COOLING CAPACITIES

Table 23 – COOLING CAPACITIES

2-STAGE COOLING

 

 

 

 

 

 

7.5 TONS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

580J08 COOLING CAPACITIES, UNIT WITH PERFECT HUMIDITY SYSTEM IN SUBCOOLING MODE

 

 

 

 

 

 

 

 

 

AIR ENTERING EVAPORATOR --- CFM

 

 

 

 

 

TEMP (F) AIR ENT

 

2250/0.05

 

 

 

 

3000/0.07

 

 

 

 

3750/0.09

 

 

CONDENSER (Edb)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air Entering Evaporator --- Ewb (F)

 

 

 

 

 

 

 

 

 

72

 

67

 

62

 

72

 

67

 

62

 

72

 

67

 

62

 

 

TC

103.05

 

93.02

 

83.60

 

109.77

 

99.52

 

90.08

 

114.01

 

103.69

 

95.19

75

 

SHC

43.66

 

55.34

 

67.09

 

50.99

 

66.29

 

81.31

 

57.49

 

76.27

 

92.20

 

 

kW

4.90

 

4.83

 

4.77

 

4.82

 

4.88

 

4.96

 

4.99

 

4.91

 

4.85

 

 

TC

95.39

 

85.83

 

76.88

 

101.59

 

91.89

 

82.95

 

105.53

 

95.76

 

87.77

85

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SHC

36.42

 

48.47

 

60.60

 

43.24

 

58.99

 

74.40

 

49.44

 

68.68

 

84.90

 

 

kW

5.49

 

5.42

 

5.36

 

5.40

 

5.47

 

5.54

 

5.58

 

5.50

 

5.44

 

 

TC

87.48

 

78.44

 

69.97

 

93.21

 

84.05

 

75.61

 

96.84

 

87.63

 

80.14

95

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SHC

28.98

 

41.46

 

53.97

 

35.32

 

51.53

 

67.34

 

41.21

 

60.92

 

77.41

 

 

kW

6.16

 

6.09

 

6.03

 

6.08

 

6.14

 

6.21

 

6.24

 

6.17

 

6.11

 

 

TC

79.35

 

70.83

 

62.84

 

84.57

 

75.96

 

68.04

 

87.88

 

79.23

 

72.26

105

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SHC

21.34

 

34.26

 

47.18

 

27.17

 

43.86

 

60.08

 

32.73

 

52.95

 

69.70

 

 

kW

6.93

 

6.86

 

6.81

 

6.85

 

6.91

 

6.97

 

7.00

 

6.93

 

6.88

 

 

TC

70.87

 

62.89

 

55.42

 

75.58

 

67.54

 

60.15

 

78.56

 

70.51

 

64.06

115

 

SHC

13.40

 

26.79

 

40.14

 

18.70

 

35.89

 

52.54

 

23.94

 

44.68

 

61.67

 

 

kW

7.79

 

7.74

 

7.69

 

7.73

 

7.78

 

7.83

 

7.86

 

7.80

 

7.76

 

 

 

 

580J08 COOLING CAPACITIES, UNIT WITH PERFECT HUMIDITY SYSTEM IN HOT GAS REHEAT MODE

 

 

 

 

 

 

 

 

 

AIR ENTERING EVAPORATOR --- Ewb (F)

 

 

 

 

 

 

 

 

 

 

75 Dry Bulb

 

 

 

 

75 Dry Bulb

 

 

 

 

75 Dry Bulb

 

TEMP (F) AIR ENT

 

62.5 Wet Bulb

 

 

 

64 Wet Bulb

 

 

 

65.3 Wet Bulb

 

CONDENSER (Edb)

 

(50% Relative)

 

 

 

(56% Relative)

 

 

 

(60% Relative)

 

 

 

 

 

 

 

 

 

Air Entering Evaporator --- Cfm

 

 

 

 

 

 

 

 

 

2250

3000

 

3750

2250

3000

 

3750

 

2250

3000

 

3750

 

 

TC

27.60

32.75

 

30.19

40.09

39.43

 

37.73

 

45.06

45.25

 

44.25

80

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SHC

--- 3.12

5.20

 

6.71

3.75

5.24

 

6.75

 

3.77

5.26

 

6.78

 

 

kW

4.56

4.51

 

4.46

4.63

4.60

 

4.56

 

4.70

4.67

 

4.64

 

 

TC

35.40

33.78

 

31.20

41.14

40.51

 

38.80

 

46.15

46.37

 

45.38

75

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SHC

4.67

6.17

 

7.69

4.71

6.21

 

7.73

 

4.74

6.24

 

7.76

 

 

kW

4.41

4.36

 

4.39

4.41

4.36

 

4.36

 

4.41

4.39

 

4.36

 

 

TC

36.36

34.71

 

32.18

42.10

41.47

 

39.77

 

47.08

47.31

 

46.32

70

 

SHC

5.63

7.14

 

8.66

5.67

7.18

 

8.71

 

5.70

7.21

 

8.74

 

 

kW

4.43

4.49

 

4.41

4.44

4.40

 

4.39

 

4.49

4.47

 

4.44

 

 

TC

38.25

36.64

 

34.15

43.97

43.37

 

41.72

 

48.98

49.22

 

48.26

60

 

SHC

7.56

9.09

 

10.62

7.60

9.13

 

10.66

 

7.62

9.15

 

10.69

 

 

kW

4.56

4.55

 

4.43

4.57

4.53

 

4.46

 

4.56

4.55

 

4.50

 

 

TC

40.15

38.60

 

36.14

45.95

45.37

 

43.73

 

50.57

50.97

 

49.56

50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SHC

9.48

11.03

 

12.58

9.52

11.07

 

12.62

 

9.54

11.10

 

12.64

 

 

kW

4.63

4.52

 

4.38

4.45

4.41

 

4.33

 

5.25

4.91

 

5.60

 

 

TC

42.18

40.62

 

38.11

47.80

47.25

 

45.43

 

52.65

52.75

 

51.83

40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SHC

11.41

12.98

 

14.54

11.45

13.02

 

14.58

 

11.47

13.04

 

14.60

 

 

kW

4.32

4.37

 

4.37

4.65

4.60

 

4.89

 

4.96

5.20

 

5.12

 

 

 

 

NOTE: Perfect Humidity only available on 2--- stage RTPF models.

NOTES:

 

 

LEGEND

 

 

 

Edb

---

Entering Dry--- Bulb

1. Direct interpolation is permissible. Do not extrapolate.

Ewb

---

Entering Wet--- Bulb

2. The following formulas may be used:

kW

---

Compressor Motor Power Input

 

sensible capacity (Btuh)

 

Idb

---

Leaving Dry--- Bulb

tldb = tedb

1.10 x cfm

Iwb

---

Leaving Wet--- Bulb

tlwb = Wet--- bulb temperature corresponding to enthalpy of air

SHC ---

Sensible Heat Capacity (1000 Btuh) Gross

leaving evaporator coil (hlwb)

TC

---

Total Capacity (1000 Btuh) Gross

 

total capacity (Btuh)

 

 

 

 

hlwb = hewb

 

 

 

4.5 x cfm

Where: hewb = Enthalpy of air entering evaporator coil

580J

43

Page 43
Image 43
Bryant 580J manual Cooling Capacities, Stagecooling, Tons