Table 26 – COOLING CAPACITIES

580J

Table 26 – COOLING CAPACITIES

2-STAGE COOLING

 

 

 

 

 

 

8.5 TONS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

580J09 COOLING CAPACITIES, UNIT WITH PERFECT HUMIDITY SYSTEM IN SUBCOOLING MODE

 

 

 

 

 

 

 

 

 

AIR ENTERING EVAPORATOR --- CFM

 

 

 

 

 

TEMP (F) AIR ENT

 

2550/0.04

 

 

 

 

3400/0.05

 

 

 

 

4250/0.07

 

 

CONDENSER (Edb)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air Entering Evaporator --- Ewb (F)

 

 

 

 

 

 

 

 

 

72

 

67

 

62

 

72

 

67

 

62

 

72

 

67

 

62

 

 

TC

119.20

 

107.44

 

96.41

 

126.95

 

114.98

 

103.92

 

131.87

 

119.81

 

109.54

75

 

SHC

50.63

 

63.94

 

77.40

 

59.17

 

76.72

 

94.21

 

66.80

 

88.44

 

108.22

 

 

kW

5.67

 

5.57

 

5.47

 

5.54

 

5.63

 

5.74

 

5.79

 

5.68

 

5.59

 

 

TC

110.40

 

99.22

 

88.76

 

117.63

 

106.26

 

95.77

 

122.21

 

110.77

 

101.07

85

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SHC

42.39

 

56.16

 

70.07

 

50.42

 

68.45

 

86.38

 

57.71

 

79.86

 

99.95

 

 

kW

6.33

 

6.23

 

6.14

 

6.20

 

6.30

 

6.40

 

6.45

 

6.34

 

6.25

 

 

TC

101.37

 

90.79

 

80.86

 

108.07

 

97.31

 

87.39

 

112.29

 

101.47

 

92.38

95

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SHC

33.97

 

48.22

 

62.56

 

41.46

 

60.01

 

78.39

 

48.40

 

71.09

 

91.47

 

 

kW

7.08

 

6.99

 

6.90

 

6.96

 

7.05

 

7.16

 

7.20

 

7.09

 

7.01

 

 

TC

92.04

 

82.06

 

72.71

 

98.19

 

88.05

 

78.72

 

102.07

 

91.86

 

83.40

105

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SHC

25.31

 

40.06

 

54.88

 

32.24

 

51.33

 

70.17

 

38.85

 

62.06

 

82.67

 

 

kW

7.94

 

7.85

 

7.77

 

7.83

 

7.91

 

8.01

 

8.06

 

7.95

 

7.87

 

 

TC

82.37

 

73.01

 

64.24

 

87.95

 

78.45

 

69.73

 

91.46

 

81.90

 

74.09

115

 

SHC

16.38

 

31.65

 

46.95

 

22.71

 

42.37

 

61.69

 

28.94

 

52.74

 

73.52

 

 

kW

8.92

 

8.84

 

8.77

 

8.82

 

8.89

 

8.98

 

9.02

 

8.93

 

8.86

 

 

 

 

580J09 COOLING CAPACITIES, UNIT WITH PERFECT HUMIDITY SYSTEM IN HOT GAS REHEAT MODE

 

 

 

 

 

 

 

 

 

AIR ENTERING EVAPORATOR --- Ewb (F)

 

 

 

 

 

 

 

 

 

 

75 Dry Bulb

 

 

 

 

75 Dry Bulb

 

 

 

 

75 Dry Bulb

 

TEMP (F) AIR ENT

 

62.5 Wet Bulb

 

 

 

64 Wet Bulb

 

 

 

65.3 Wet Bulb

 

CONDENSER (Edb)

 

(50% Relative)

 

 

 

(56% Relative)

 

 

 

(60% Relative)

 

 

 

 

 

 

 

 

 

Air Entering Evaporator --- Cfm

 

 

 

 

 

 

 

 

 

2550

3400

 

4250

2550

3400

 

4250

 

2550

3400

 

4250

 

 

TC

37.61

33.13

 

26.77

44.74

41.60

 

36.46

 

50.96

48.99

 

44.93

80

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SHC

--- 0.52

--- 0.63

 

--- 0.73

--- 0.46

--- 0.57

 

--- 0.67

 

--- 0.42

--- 0.53

 

--- 0.62

 

 

kW

5.88

5.68

 

5.44

6.13

5.97

 

5.76

 

6.35

6.24

 

6.06

 

 

TC

38.71

34.24

 

27.86

45.84

42.73

 

37.59

 

52.05

50.11

 

46.06

75

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SHC

0.45

0.34

 

0.25

0.50

0.40

 

0.31

 

0.54

0.44

 

0.36

 

 

kW

5.68

5.47

 

5.22

5.94

5.78

 

5.56

 

6.18

6.07

 

5.88

 

 

TC

39.70

35.25

 

28.83

46.80

43.70

 

38.59

 

52.97

51.04

 

47.02

70

 

SHC

1.41

1.32

 

1.23

1.47

1.37

 

1.29

 

1.50

1.41

 

1.34

 

 

kW

5.65

5.42

 

5.24

5.97

5.79

 

5.53

 

6.26

6.13

 

5.91

 

 

TC

41.77

37.33

 

30.76

48.86

45.80

 

40.71

 

55.00

53.10

 

49.12

60

 

SHC

3.34

3.26

 

3.18

3.40

3.32

 

3.25

 

3.43

3.36

 

3.29

 

 

kW

5.42

5.15

 

5.17

5.80

5.59

 

5.30

 

6.16

6.01

 

5.75

 

 

TC

43.83

39.27

 

32.61

50.92

47.89

 

42.70

 

57.04

55.16

 

51.22

50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SHC

5.27

5.21

 

5.14

5.32

5.27

 

5.21

 

5.36

5.31

 

5.25

 

 

kW

5.18

5.15

 

5.17

5.62

5.39

 

5.05

 

6.04

5.87

 

5.59

 

 

TC

45.75

41.13

 

34.50

53.08

50.00

 

44.64

 

59.24

57.40

 

53.44

40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SHC

7.20

7.15

 

6.95

7.26

7.21

 

7.16

 

7.29

7.25

 

7.21

 

 

kW

4.79

4.98

 

4.80

5.25

5.01

 

5.23

 

5.68

5.51

 

5.21

 

 

 

 

NOTE: Perfect Humidity only available on 2--- stage RTPF models.

NOTES:

 

 

LEGEND

 

 

 

Edb

---

Entering Dry--- Bulb

1. Direct interpolation is permissible. Do not extrapolate.

Ewb

---

Entering Wet--- Bulb

2. The following formulas may be used:

kW

---

Compressor Motor Power Input

 

sensible capacity (Btuh)

 

Idb

---

Leaving Dry--- Bulb

tldb = tedb

1.10 x cfm

Iwb

---

Leaving Wet--- Bulb

tlwb = Wet--- bulb temperature corresponding to enthalpy of air

SHC ---

Sensible Heat Capacity (1000 Btuh) Gross

leaving evaporator coil (hlwb)

TC

---

Total Capacity (1000 Btuh) Gross

 

total capacity (Btuh)

 

 

 

 

hlwb = hewb

 

 

 

4.5 x cfm

Where: hewb = Enthalpy of air entering evaporator coil

46

Page 46
Image 46
Bryant 580J manual Cooling Capacities, Stagecooling, Tons