Bryant 580J manual Cooling Capacities, Stagecooling, Tons

Models: 580J

1 94
Download 94 pages 40.55 Kb
Page 34
Image 34
Table 14 – COOLING CAPACITIES
tldb = tedb

580J

Table 14 – COOLING CAPACITIES

1-STAGE COOLING

 

 

 

3 TONS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

580J04 (3 TONS) --- UNIT WITH PERFECT HUMIDITY SYSTEM IN SUBCOOLING MODE

 

 

 

 

 

 

Air Entering Evaporator --- CFM

 

 

 

 

Temp (F) Air Ent

 

 

80 dry bulb

 

 

80 dry bulb

 

 

80 dry bulb

 

 

 

72 wet bulb

 

 

67 wet bulb

 

 

62 wet bulb

 

Condenser (Edb)

 

 

 

 

 

 

 

 

 

 

900

1200

1500

900

1200

1500

900

1200

1500

 

TC

 

40.6

43.2

45.3

37.0

39.4

41.3

33.4

35.6

37.4

75

SHC

 

21.6

23.9

25.6

25.6

27.7

29.3

29.6

31.6

33.1

 

kW

 

2.0

2.0

2.0

2.0

2.0

2.0

2.0

2.0

2.0

 

TC

 

37.0

39.6

41.7

33.6

36.0

37.9

30.2

32.3

34.1

85

SHC

 

17.7

20.2

22.2

22.7

25.0

26.9

27.7

29.9

31.6

 

kW

 

2.3

2.3

2.3

2.3

2.3

2.3

2.3

2.3

2.3

 

TC

 

33.5

36.0

38.1

30.2

32.5

34.4

26.9

29.1

30.8

95

 

 

 

 

 

 

 

 

 

 

 

SHC

 

13.7

16.6

18.8

19.7

22.4

24.4

25.7

28.2

30.1

 

kW

 

2.6

2.6

2.6

2.5

2.5

2.5

2.5

2.5

2.5

 

TC

 

29.9

32.4

34.5

26.8

29.1

31.0

23.6

25.8

27.5

105

 

 

 

 

 

 

 

 

 

 

 

SHC

 

9.8

12.9

15.3

16.8

19.7

22.0

23.8

26.5

28.6

 

kW

 

2.9

2.9

2.9

2.8

2.8

2.8

2.8

2.8

2.8

 

TC

 

26.3

28.8

30.9

23.3

25.7

27.5

20.4

22.5

24.2

115

SHC

 

5.8

9.2

11.9

13.8

17.0

19.5

21.9

24.8

27.1

 

kW

 

3.2

3.2

3.2

3.1

3.1

3.1

3.1

3.1

3.1

 

 

 

 

 

 

580J04 (3 TONS) --- UNIT WITH PERFECT HUMIDITY SYSTEM IN HOT GAS REHEAT MODE

 

 

 

 

 

 

Air Entering Evaporator --- CFM

 

 

 

 

Temp (F) Air Ent

 

 

75 dry bulb

 

 

75 dry bulb

 

 

75 dry bulb

 

 

62.5 wet bulb (50% relative)

64 wet bulb (55% relative)

65.3 wet bulb (60% relative)

Condenser (Edb)

 

 

 

 

1050

1200

1350

1050

1200

1350

1050

1200

1350

 

TC

 

14.7

15.5

16.2

15.9

16.7

17.4

16.9

17.7

18.4

80

SHC

 

6.7

7.6

8.5

4.8

5.7

6.6

3.2

4.1

5.0

 

kW

 

2.0

2.0

2.0

2.0

2.0

2.0

2.0

2.0

2.0

 

TC

 

15.1

15.8

16.4

16.2

17.0

17.6

17.2

18.0

18.6

75

SHC

 

7.5

8.4

9.2

5.8

6.7

7.5

4.4

5.2

6.0

 

kW

 

1.9

1.9

1.9

2.0

2.0

2.0

2.0

2.0

2.0

 

TC

 

15.5

16.1

16.7

16.6

17.3

17.9

17.5

18.2

18.8

70

 

 

 

 

 

 

 

 

 

 

 

SHC

 

8.4

9.3

10.0

6.9

7.7

8.5

5.5

6.4

7.1

 

kW

 

1.9

1.9

1.9

1.9

1.9

1.9

1.9

1.9

1.9

 

TC

 

16.2

16.8

17.3

17.2

17.8

18.3

18.1

18.7

19.2

60

 

 

 

 

 

 

 

 

 

 

 

SHC

 

10.2

10.9

11.6

8.9

9.7

10.4

7.8

8.6

9.3

 

kW

 

1.8

1.8

1.8

1.8

1.8

1.8

1.9

1.9

1.9

 

TC

 

17.0

17.5

17.9

17.9

18.4

18.8

18.7

19.2

19.6

50

SHC

 

11.9

12.6

13.2

11.0

11.6

12.2

10.1

10.8

11.4

 

kW

 

1.7

1.7

1.7

1.8

1.8

1.8

1.8

1.8

1.8

 

TC

 

17.7

18.1

18.5

18.6

19.0

19.3

19.3

19.7

20.1

40

SHC

 

13.7

14.3

14.8

13.0

13.6

14.1

12.4

13.0

13.5

 

kW

 

1.7

1.7

1.7

1.7

1.7

1.7

1.7

1.7

1.7

LEGEND

 

Edb

---

Entering Dry--- Bulb

Ewb

---

Entering Wet--- Bulb

kW

---

Compressor Motor Power Input

Idb

---

Leaving Dry--- Bulb

Iwb

---

Leaving Wet--- Bulb

SHC ---

Sensible Heat Capacity (1000 Btuh) Gross

TC

---

Total Capacity (1000 Btuh) Gross

NOTES:

1.Direct interpolation is permissible. Do not extrapolate.

2.The following formulas may be used:

sensible capacity (Btuh)

1.10 x cfm

tlwb = Wet--- bulb temperature corresponding to enthalpy of air leaving evaporator coil (hlwb)

total capacity (Btuh)

hlwb = hewb 4.5 x cfm

Where: hewb = Enthalpy of air entering evaporator coil

34

Page 34
Image 34
Bryant 580J manual Cooling Capacities, Stagecooling, Tons