Table 40 – 580J**05

FAN PERFORMANCE (cont.)

Table 40 – 580J**05

 

 

3 PHASE

 

4 TON HORIZONTAL SUPPLY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

CFM

 

0.2

 

0.4

0.6

 

0.8

 

 

1.0

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

 

Standard Static Option

 

 

Medium Static Option

 

 

1200

643

0.23

762

0.34

859

0.46

944

0.58

1020

0.71

1300

675

0.28

790

0.40

886

0.52

969

0.65

1044

0.78

1400

707

0.33

819

0.45

913

0.58

996

0.72

1070

0.86

1500

740

0.38

849

0.52

941

0.66

1023

0.80

1096

0.95

1600

773

0.45

 

 

970

0.73

1050

0.88

1123

1.04

879

0.59

1700

807

0.52

910

0.67

999

0.82

1078

0.98

1150

1.14

1800

841

0.59

942

0.75

1029

0.91

1106

1.08

 

 

1177

1.25

1900

875

0.68

974

0.85

1059

1.02

1135

1.19

1205

1.37

2000

910

0.77

1006

0.95

1090

1.13

1165

1.31

1234

1.49

 

 

 

 

 

 

 

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

CFM

 

1.2

 

1.4

1.6

 

1.8

 

 

2.0

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

 

Medium Static Option

 

 

 

High Static Option

 

 

1200

1089

0.84

1153

0.98

1213

1.12

1270

1.27

1324

1.42

1300

1113

0.92

1177

1.06

1237

1.21

1293

1.36

1347

1.52

1400

1138

1.01

1201

1.15

1261

1.31

1317

1.47

1370

1.63

1500

1163

1.10

1226

1.25

1285

1.41

1341

1.58

1394

1.75

1600

 

 

1252

1.36

1310

1.53

1365

1.70

1418

1.87

1189

1.20

1700

1216

1.31

1277

1.48

1335

1.65

1390

1.83

1442

2.01

1800

1242

1.42

1303

1.60

1361

1.78

1415

1.96

1467

2.15

1900

1270

1.55

1330

1.73

1387

1.92

1441

2.11

 

 

1493

2.30

2000

1297

1.68

1357

1.87

1414

2.07

1467

2.26

---

---

 

 

 

 

 

 

 

 

 

 

 

NOTE: For more information, see General Fan Performance Notes. Boldface indicates field supplied drive is required.

1. Recommend using field supplied fan pulley (part no. KR11AZ506), motor pulley (part no. KR11HY181) and belt (part no. KR30AE041).

Table 41 – 580J**05

 

 

3 PHASE

 

 

4 TON VERTICAL SUPPLY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

CFM

 

0.2

 

0.4

0.6

 

0.8

 

 

1.0

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

 

Standard Static Option

 

 

Medium Static Option

 

 

1200

666

0.26

778

0.37

871

0.47

952

0.57

1025

0.67

1300

701

0.31

810

0.43

901

0.54

981

0.65

1053

0.76

1400

737

0.36

842

0.49

931

0.62

1010

0.74

1081

0.86

1500

773

0.42

 

 

963

0.70

1040

0.84

1110

0.96

875

0.57

1600

810

0.49

909

0.65

994

0.79

1070

0.94

1140

1.08

1700

847

0.57

943

0.73

1027

0.89

1101

1.05

1170

1.20

1800

 

 

978

0.83

1060

1.00

1133

1.16

 

 

885

0.66

1200

1.32

1900

923

0.75

1014

0.94

1093

1.11

1165

1.29

1231

1.46

2000

962

0.85

1049

1.05

1127

1.24

1198

1.42

1263

1.61

 

 

 

 

 

 

 

 

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

CFM

 

1.2

 

1.4

1.6

 

1.8

 

 

2.0

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

 

Medium Static Option

 

 

 

High Static Option

 

 

1200

1093

0.77

1155

0.87

1213

0.96

1268

1.05

1321

1.14

1300

1119

0.87

1181

0.98

1239

1.08

1294

1.18

1346

1.28

1400

1147

0.98

1208

1.09

1265

1.21

1320

1.32

1371

1.43

1500

1175

1.09

1235

1.22

1292

1.34

1346

1.46

1397

1.58

1600

 

 

1263

1.35

1320

1.48

1373

1.61

1424

1.74

1204

1.21

1700

1233

1.34

1292

1.49

1348

1.63

1401

1.77

1451

1.91

1800

1262

1.48

1321

1.64

1376

1.79

1428

1.94

1479

2.09

1900

1293

1.63

1350

1.79

1405

1.96

1457

2.12

 

 

1506

2.28

2000

1323

1.79

1380

1.96

1434

2.13

1486

2.31

---

---

NOTE: For more information, see General Fan Performance Notes. Boldface indicates field supplied drive is required.

1. Recommend using field supplied fan pulley (part no. KR11AZ506), motor pulley (part no. KR11HY181) and belt (part no. KR30AE041).